Second Harmonic-Based Approach to Identify a GIC Flow in Power Transformers

Certain parts of the world can experience active geomagnetic disturbances, which trigger the flow of geomagnetically induced currents (GICs) through grounding circuits into power systems. Such currents are quasi-dc currents that can have large magnitudes capable of inflecting damage to power system equipment. Power transformers are among the vulnerable equipment to GIC flows, which can cause harmonic distortion, disruption in reactive power flow, and thermal damage in transformer windings. Adverse effects of GIC flows can be minimized by developing a fast, accurate, and reliable detection method of GICs. Such a detection method can support initiating adequate responses to block the GIC from flowing into power transformers. This paper presents the development and implementation of a method to detect GIC flows in power transformers. The developed method is based on extracting the second harmonic present in the differential currents. The proposed GIC detection is experimentally tested using laboratory <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$3\phi$</tex-math></inline-formula> transformers, when operated for different GIC flows and loading levels. In addition, experimental tests are conducted for magnetizing inrush currents and various faults in both sides of tested transformers. Test results demonstrate fast and accurate detection of GIC flows with minor sensitivity to the value of the GIC, loading level, and/or transformer core type. In addition, the proposed <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$2{\text{nd}}$</tex-math></inline-formula> harmonic-based method is found able to accurately distinguish GIC flows from magnetizing inrush and fault currents.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Industry Applications
Published
2024-12-26
DOI
https://doi.org/10.1109/tia.2024.3522875
Citations
6
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
1.25
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Second Harmonic-Based Approach to Identify a GIC Flow in Power Transformers

S. A. Saleh, Julian Meng, M. Bourque, S. Brown et al.
6 citations
IEEE Transactions on Industry Applications
Power Transformer Diagnostics and Insulation
1.25
article

Second Harmonic-Based Approach to Identify a GIC Flow in Power Transformers

S. A. Saleh, Julian Meng, M. Bourque, S. Brown, E. W. Zundel, G. Young-Morris, E.F. Hill
article en
6 citations

Abstract

Certain parts of the world can experience active geomagnetic disturbances, which trigger the flow of geomagnetically induced currents (GICs) through grounding circuits into power systems. Such currents are quasi-dc currents that can have large magnitudes capable of inflecting damage to power system equipment. Power transformers are among the vulnerable equipment to GIC flows, which can cause harmonic distortion, disruption in reactive power flow, and thermal damage in transformer windings. Adverse effects of GIC flows can be minimized by developing a fast, accurate, and reliable detection method of GICs. Such a detection method can support initiating adequate responses to block the GIC from flowing into power transformers. This paper presents the development and implementation of a method to detect GIC flows in power transformers. The developed method is based on extracting the second harmonic present in the differential currents. The proposed GIC detection is experimentally tested using laboratory <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$3\phi$</tex-math></inline-formula> transformers, when operated for different GIC flows and loading levels. In addition, experimental tests are conducted for magnetizing inrush currents and various faults in both sides of tested transformers. Test results demonstrate fast and accurate detection of GIC flows with minor sensitivity to the value of the GIC, loading level, and/or transformer core type. In addition, the proposed <inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"><tex-math notation="LaTeX">$2{\text{nd}}$</tex-math></inline-formula> harmonic-based method is found able to accurately distinguish GIC flows from magnetizing inrush and fault currents.

IEEE Transactions on Industry ApplicationsVol. 61(2)
University of New Brunswick (CA), Energie NB Power (Canada) (CA)
Affordable and clean energy
Openalex Percentile: Top 19%
Power Transformer Diagnostics and Insulation
1.25
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.