Magnetic field normalization in residential premises located above built-in transformer substations 6(10)/0,4 kV power 100-400 kVA

The purpose of the work is to define methods and means of screening, sufficient to reduce to a safe level the low frequency magnetic field in residential premises of old buildings, located above built-in transformer substations 6(10)/0,4 kV power 100–400 kVA at short distances to the premises. To achieve this goal, a modified method for synthesizing active shielding systems of the magnetic field for transformer substations at short distances from the substation to the floor of the premises, and its experimental verification was carried out on a full-scale physical model of a transformer substation power 100 kVA with a physical layout of the synthesized active shielding system. A synthesis of active shielding systems of magnetic field for transformer substations with a power of 100–400 kVA at short distances from the substation to the floor of the premises and an analysis of their effectiveness were carried out. It was determined that the normalization of the magnetic field on the floor surface for transformer substations with a power of 100 kVA using a synthesized active shielding system with one compensation winding is possible at distances of at least 1,15 m from the substation, and with two windings - at least 1,02 m. It was determined that normalization of the magnetic field on the floor surface for 400 kVA transformer substations using a synthesized active shielding system with two windings is possible only at a distance from the substation of at least 1,6 m. An analysis of the effectiveness of the combined use of active and passive shielding was conducted. It was determined that the combined use of synthesized two-channel active shielding systems and a passive flat electromagnetic shield made of 4 mm thick aluminum sheet allows reducing the magnetic field above the built-in transformer substation with a power of 100 to 400 kVA to the normative level while limiting the distance from the substation to the floor of the premises to at least 1,08 m and provides protection of public health from the effects of the low frequency magnetic field.

Authors

Institutions

Publication Details

Journal
Bulletin of NTU KhPI Series Problems of Electrical Machines and Apparatus Perfection The Theory and Practice
Published
2024-12-26
DOI
https://doi.org/10.20998/2079-3944.2024.2.08
Primary Topic
Electromagnetic Fields and Biological Effects
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Magnetic field normalization in residential premises located above built-in transformer substations 6(10)/0,4 kV power 100-400 kVA

D. Ye. Pelevin
Bulletin of NTU KhPI Series Problems of Electrical Machines and Apparatus Perfection The Theory and Practice
Electromagnetic Fields and Biological Effects
article

Magnetic field normalization in residential premises located above built-in transformer substations 6(10)/0,4 kV power 100-400 kVA

D. Ye. Pelevin
article en

Abstract

The purpose of the work is to define methods and means of screening, sufficient to reduce to a safe level the low frequency magnetic field in residential premises of old buildings, located above built-in transformer substations 6(10)/0,4 kV power 100–400 kVA at short distances to the premises. To achieve this goal, a modified method for synthesizing active shielding systems of the magnetic field for transformer substations at short distances from the substation to the floor of the premises, and its experimental verification was carried out on a full-scale physical model of a transformer substation power 100 kVA with a physical layout of the synthesized active shielding system. A synthesis of active shielding systems of magnetic field for transformer substations with a power of 100–400 kVA at short distances from the substation to the floor of the premises and an analysis of their effectiveness were carried out. It was determined that the normalization of the magnetic field on the floor surface for transformer substations with a power of 100 kVA using a synthesized active shielding system with one compensation winding is possible at distances of at least 1,15 m from the substation, and with two windings - at least 1,02 m. It was determined that normalization of the magnetic field on the floor surface for 400 kVA transformer substations using a synthesized active shielding system with two windings is possible only at a distance from the substation of at least 1,6 m. An analysis of the effectiveness of the combined use of active and passive shielding was conducted. It was determined that the combined use of synthesized two-channel active shielding systems and a passive flat electromagnetic shield made of 4 mm thick aluminum sheet allows reducing the magnetic field above the built-in transformer substation with a power of 100 to 400 kVA to the normative level while limiting the distance from the substation to the floor of the premises to at least 1,08 m and provides protection of public health from the effects of the low frequency magnetic field.

Bulletin of NTU KhPI Series Problems of Electrical Machines and Apparatus Perfection The Theory and Practice(2 (12))
Weatherford College (US)
Sustainable cities and communities
Openalex Percentile: Top 84%
Electromagnetic Fields and Biological Effects
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.