Strategy for Energy Savings in a Commercial Building Air-conditioning System with Chilled Water Storage: A Case Study in a Retail Mall in Thailand

In this study, a commercial retail mall is used as a case study to integrate a chilled water storage (CHWS) with the existing chilled water system to reduce electrical energy consumption and capitalize on the economic benefits of electrical energy saving cost and the differential between on-peak and off-peak tariffs. This study aims to improve the chiller efficiency in three operating strategies: full storage, partial storage load leveling, and partial storage demand limiting, by operating the chillers at optimal part load conditions. Technical and economic assessments were conducted to determine the necessary storage capacity and appropriate operational strategies. In comparison to the existing operation, which uses two 800 RT chillers continuously during on-peak hours and one chiller operating at 20-30% capacity during off-peak hours, the proposed systems: three 800 RT chillers with a 9,150 m³ tank for full storage, one 800 RT and one 260 RT chiller with a 3,292 m³ tank for partial load leveling, and two 800 RT chillers with a 4,987 m³ tank for partial demand limiting, demonstrate significant potential to reduce electrical energy consumption. The full storage strategy achieves the lowest electrical energy consumption, followed by partial demand limiting and partial load leveling. Economically, partial demand limiting strategy emerges as the most feasible, providing a payback period of 7.42 years and an internal rate of return (IRR) of 14.92%. This is more favorable compared to payback periods of 8.6 and 9.65 years and internal rate of return of 12.08 and 10.33% for partial load leveling and full storage strategies, respectively.

Authors

Institutions

Publication Details

Journal
Journal of Current Science and Technology
Published
2024-12-24
DOI
https://doi.org/10.59796/jcst.v15n1.2025.89
Citations
1
Primary Topic
Smart Grid Energy Management
Type
article
Field-Weighted Citation Impact
0.21

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Strategy for Energy Savings in a Commercial Building Air-conditioning System with Chilled Water Storage: A Case Study in a Retail Mall in Thailand

Tanongkiat Kiatsiriroat, Attakorn Asanakham, Thoranis Deethayat, Nang San Khun
1 citations
Journal of Current Science and Technology
Smart Grid Energy Management
0.21
article

Strategy for Energy Savings in a Commercial Building Air-conditioning System with Chilled Water Storage: A Case Study in a Retail Mall in Thailand

Tanongkiat Kiatsiriroat, Attakorn Asanakham, Thoranis Deethayat, Nang San Khun
article en
1 citations

Abstract

In this study, a commercial retail mall is used as a case study to integrate a chilled water storage (CHWS) with the existing chilled water system to reduce electrical energy consumption and capitalize on the economic benefits of electrical energy saving cost and the differential between on-peak and off-peak tariffs. This study aims to improve the chiller efficiency in three operating strategies: full storage, partial storage load leveling, and partial storage demand limiting, by operating the chillers at optimal part load conditions. Technical and economic assessments were conducted to determine the necessary storage capacity and appropriate operational strategies. In comparison to the existing operation, which uses two 800 RT chillers continuously during on-peak hours and one chiller operating at 20-30% capacity during off-peak hours, the proposed systems: three 800 RT chillers with a 9,150 m³ tank for full storage, one 800 RT and one 260 RT chiller with a 3,292 m³ tank for partial load leveling, and two 800 RT chillers with a 4,987 m³ tank for partial demand limiting, demonstrate significant potential to reduce electrical energy consumption. The full storage strategy achieves the lowest electrical energy consumption, followed by partial demand limiting and partial load leveling. Economically, partial demand limiting strategy emerges as the most feasible, providing a payback period of 7.42 years and an internal rate of return (IRR) of 14.92%. This is more favorable compared to payback periods of 8.6 and 9.65 years and internal rate of return of 12.08 and 10.33% for partial load leveling and full storage strategies, respectively.

Journal of Current Science and TechnologyVol. 15(1)
Chiang Mai University (TH)
Chiang Mai University
Affordable and clean energy
Openalex Percentile: Top 45%
Smart Grid Energy Management
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.