Power Flow Analysis of Ring AC/DC Hybrid Network with Multiple Power Electronic Transformers Based on Hybrid Alternating Iteration Power Flow Algorithm
AC/DC hybrid distribution networks with power electronic transformers (PETs) as distribution hubs are in line with the future development direction of the AC/DC hybrid distribution network. Unlike traditional transformers, power electronic transformers introduce new node types and may transform the network topology from radial to ring structures. These changes render traditional power flow calculation methods inadequate for achieving satisfactory results in AC/DC hybrid networks. In addition, existing commercial power flow calculation software packages are mainly based on the traditional AC power flow calculation method, which have limited support for the DC network. Especially when the DC network is coupled with the AC network, it is difficult to achieve a unified calculation of its power flow. To address these challenges, this paper proposes a novel power flow calculation method for ring AC/DC hybrid distribution networks with power electronic transformers. The proposed method is based on the alternating iterative method to ensure compatibility with mature AC power flow calculation programs in commercial software, thereby improving the feasibility of engineering applications. Firstly, the steady-state power flow calculation model of PET is constructed by analyzing that the working principle and control modes of power electronic transformer are proposed based on the source-load attributes of its connected subnetworks. According to the characteristics of the power electronic transformer, AC distribution network, and DC distribution network, a hybrid alternating iteration method combining the high computational accuracy of the Newton–Raphson (NR) method with the high efficiency of the Zbus Gaussian method in dealing with ring networks is proposed. On this basis, the power flow calculation model of the AC/DC hybrid distribution network with power electronic transformers is established. Finally, the simulation of the constructed 44-node ring AC/DC hybrid distribution network example is carried out. The simulation results show that the proposed method can not only converge reliably when the convergence accuracy is 1 × 10−6 p.u., but also ensure that the voltage magnitudes of all nodes are above 0.96 p.u. whose maximum offset value is 0.789% when the outputs of the connected distributed generations fluctuate, which verifies the effectiveness and accuracy of the proposed method.
Authors
- Yinan Huang (ORCID: https://orcid.org/0000-0002-9579-4119)
- Zhen Zheng
- Min Wang (ORCID: https://orcid.org/0000-0001-7961-2576)
- Dongqian Pan
- Xiaoli Ma
- Wenwen Chen (ORCID: https://orcid.org/0000-0003-0975-0839)
- Chenhong Huang
Institutions
- Hohai University (CN)
- Shanghai Electric (China) (CN)
Publication Details
- Journal
- Processes
- Published
- 2024-12-24
- DOI
- https://doi.org/10.3390/pr13010007
- Citations
- 4
- Primary Topic
- HVDC Systems and Fault Protection
- Type
- article
- Field-Weighted Citation Impact
- 0.83