Pre-Arcing Characteristics of Different Rated Current Fuses in Parallel

Fuses are still widely used in power systems. However, the weak ability of low overload current disconnection restricts its application. To reduce the lower limit of the low overload interrupting capability of the fuse, this paper proposes a fuse design using different rated current fuses in parallel. In several times of experiments, the fuses with larger rated current are fused first, and then the current is broken by the fuses with smaller rated currents. This process has a higher current density on the fuses with a smaller rated current, which is helpful to the interrupting of overload fault. Compared with the traditional parallel design of the same fuse, the success rate of the parallel design of different rated current fuses is higher when the current is small. Finally, through the analysis of the I-t characteristic curve before the arc of the fuse, it is found that the uneven current distribution and I-t characteristic point movement are the reasons for the above experimental results.

Authors

Institutions

Publication Details

Published
2024-11-10
DOI
https://doi.org/10.1109/icepe-st61894.2024.10792455
Primary Topic
Electrical Fault Detection and Protection
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Pre-Arcing Characteristics of Different Rated Current Fuses in Parallel

Bin Xiang, Yingsan Geng, Zhiyuan Liu, Jianhua Wang et al.
Electrical Fault Detection and Protection
article

Pre-Arcing Characteristics of Different Rated Current Fuses in Parallel

Bin Xiang, Yingsan Geng, Zhiyuan Liu, Jianhua Wang, Dongyu Wang, Huixin Du
article en

Abstract

Fuses are still widely used in power systems. However, the weak ability of low overload current disconnection restricts its application. To reduce the lower limit of the low overload interrupting capability of the fuse, this paper proposes a fuse design using different rated current fuses in parallel. In several times of experiments, the fuses with larger rated current are fused first, and then the current is broken by the fuses with smaller rated currents. This process has a higher current density on the fuses with a smaller rated current, which is helpful to the interrupting of overload fault. Compared with the traditional parallel design of the same fuse, the success rate of the parallel design of different rated current fuses is higher when the current is small. Finally, through the analysis of the I-t characteristic curve before the arc of the fuse, it is found that the uneven current distribution and I-t characteristic point movement are the reasons for the above experimental results.

State Key Laboratory of Electrical Insulation and Power Equipment, Xi'an Jiaotong University (CN)
State Key Laboratory of Electrical Insulation and Power Equipment
Affordable and clean energy
Openalex Percentile: Top 78%
Electrical Fault Detection and Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Pre-Arcing Characteristics of Different Rated Current Fuses in Parallel — Bin Xiang, Yingsan Geng, et al. · (2024) | TGRS Research Map | TGRS