Contact Erosion at High Currents in High-Voltage Gas Circuit Breakers—Part II: Assessment of Energy Balance of Arc-Electrode

In high-voltage gas circuit breakers, arc-electrode interaction plays an important role during current interruption. The energy exchanges of arc-electrode not only influence the arc energy balance but also induce irreversible electrode erosion. To estimate the non-negligible amount of energy provided by the arc column through radiation, parameters related to the arc erosion should be fully used, including the area of molten pool, the thickness of molten layer, the effective voltage drop, etc. Under the free-burning conditions with a peak current of 40 kA and an arcing duration of 10 ms, the energy radiated from the CO<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub> arc to the electrode surface accounts for 42.5% to 50.5% of the total energy absorbed by the contact material, which is higher than that of SF<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub> (34.5%–44.3%). The equivalent voltage drop is defined for the energy transferred from arc column to electrode surface through radiation. It has been found that the equivalent voltage drop of the anode by arc radiation is from 7.7 V to 10.6 V in CO<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>, and the range is 5.4–8.1 V in SF<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>. These parameters can be utilized to accurately predict the mass loss of Cu-W contacts in gas circuit breakers following high-current interruption tests.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Power Delivery
Published
2024-12-18
DOI
https://doi.org/10.1109/tpwrd.2024.3519952
Citations
4
Primary Topic
Vacuum and Plasma Arcs
Type
article
Field-Weighted Citation Impact
1.35
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Contact Erosion at High Currents in High-Voltage Gas Circuit Breakers—Part II: Assessment of Energy Balance of Arc-Electrode

James Humphries, Jiu Dun Yan, J. W. Spencer, Yannan Zhou et al.
4 citations
IEEE Transactions on Power Delivery
Vacuum and Plasma Arcs
1.35
article

Contact Erosion at High Currents in High-Voltage Gas Circuit Breakers—Part II: Assessment of Energy Balance of Arc-Electrode

James Humphries, Jiu Dun Yan, J. W. Spencer, Yannan Zhou, Zhixiang Wang, G.R. Jones
article en
4 citations

Abstract

In high-voltage gas circuit breakers, arc-electrode interaction plays an important role during current interruption. The energy exchanges of arc-electrode not only influence the arc energy balance but also induce irreversible electrode erosion. To estimate the non-negligible amount of energy provided by the arc column through radiation, parameters related to the arc erosion should be fully used, including the area of molten pool, the thickness of molten layer, the effective voltage drop, etc. Under the free-burning conditions with a peak current of 40 kA and an arcing duration of 10 ms, the energy radiated from the CO<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub> arc to the electrode surface accounts for 42.5% to 50.5% of the total energy absorbed by the contact material, which is higher than that of SF<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub> (34.5%–44.3%). The equivalent voltage drop is defined for the energy transferred from arc column to electrode surface through radiation. It has been found that the equivalent voltage drop of the anode by arc radiation is from 7.7 V to 10.6 V in CO<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">2</sub>, and the range is 5.4–8.1 V in SF<sub xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink">6</sub>. These parameters can be utilized to accurately predict the mass loss of Cu-W contacts in gas circuit breakers following high-current interruption tests.

IEEE Transactions on Power DeliveryVol. 40(2)
University of Liverpool (GB)
Openalex Percentile: Top 19%
Vacuum and Plasma Arcs
1.35
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.