A Rack-Mounted Natural Cooling UPS Having Ultra-Wide-Efficient Load Range
A rack-mounted natural-cooling RMN uninterruptible power supply UPS having ultra-width-efficient load range, 96% efficiency from 10% load, is proposed. It is based on paralleling multiple multilevel converter modules on an efficient cooling base plate. A load-base active module control AMC is proposed to determine the suitable number of active module(s) to achieve high efficiency across the entire load range. By using the new design of heat pipe and heatsink integration and together with high operation efficiency, the proposed UPS can be running without force-air cooling. A 10kW, 220V/50Hz experimental prototype has been built and evaluated.
Authors
- Peter Chow
- River Tin-Ho Li (ORCID: https://orcid.org/0000-0001-5537-4083)
- Victor Sui-pung Cheung
- Terence Chung-Yin Lau
- Changqing Yin
Institutions
- Applied Science and Technology Research Institute (CN)
Publication Details
- Published
- 2024-11-08
- DOI
- https://doi.org/10.1109/isesc63657.2024.10785285
- Primary Topic
- Building Energy and Comfort Optimization
- Type
- article
- Field-Weighted Citation Impact
- 0.00