Data Center Waste Heat Reuse: An Investment Analysis

Abstract A thermo-economic analysis (TEA) of a novel cooling and enhanced heat recovery (CEHR) system for data centers (DCs) is presented. Three financial metrics (net present value—NPV, return on investment—ROI, and payback period—PP) are calculated for hot and chilled water generation. Hot water generation uses vapor recompression to produce water at approximately 75 °C. Chilled water generation builds upon the hot water generation scenario by feeding the hot water stream into an absorption chiller. Without considering the additional costs for connecting the infrastructure with the customer, a payback period shorter than 2 years is found for a hot water generation system for a base case assuming a 10-MW data center (DC) in Philadelphia, PA, when carbon (reduction) credits are included. Chilled water generation is found to be economically unfavorable in this location. Sensitivities of economics to data center power, hot water versus chilled water generation, geographic region, and carbon credits are evaluated for five additional global locations in Europe and Asia. The economies of scale enable favorable payback periods for integrating hot water generation for facilities beyond 7 MW. Hot water generation is especially favorable in Singapore when replacing natural gas-based heating or hot water heat pumps.

Authors

Institutions

Publication Details

Journal
ASME Journal of Engineering for Sustainable Buildings and Cities
Published
2024-12-13
DOI
https://doi.org/10.1115/1.4067444
Citations
3
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
0.64

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Data Center Waste Heat Reuse: An Investment Analysis

Aaron P. Wemhoff, Rehan Khalid, Steven Schon, Mai Khuc et al.
3 citations
ASME Journal of Engineering for Sustainable Buildings and Cities
Heat Transfer and Optimization
0.64
article

Data Center Waste Heat Reuse: An Investment Analysis

Aaron P. Wemhoff, Rehan Khalid, Steven Schon, Mai Khuc, Ajay J. Nayar
article en
3 citations

Abstract

Abstract A thermo-economic analysis (TEA) of a novel cooling and enhanced heat recovery (CEHR) system for data centers (DCs) is presented. Three financial metrics (net present value—NPV, return on investment—ROI, and payback period—PP) are calculated for hot and chilled water generation. Hot water generation uses vapor recompression to produce water at approximately 75 °C. Chilled water generation builds upon the hot water generation scenario by feeding the hot water stream into an absorption chiller. Without considering the additional costs for connecting the infrastructure with the customer, a payback period shorter than 2 years is found for a hot water generation system for a base case assuming a 10-MW data center (DC) in Philadelphia, PA, when carbon (reduction) credits are included. Chilled water generation is found to be economically unfavorable in this location. Sensitivities of economics to data center power, hot water versus chilled water generation, geographic region, and carbon credits are evaluated for five additional global locations in Europe and Asia. The economies of scale enable favorable payback periods for integrating hot water generation for facilities beyond 7 MW. Hot water generation is especially favorable in Singapore when replacing natural gas-based heating or hot water heat pumps.

ASME Journal of Engineering for Sustainable Buildings and CitiesVol. 6(1)
Villanova University (US)
Directorate for Engineering
Industry, innovation and infrastructure
Openalex Percentile: Top 34%
Heat Transfer and Optimization
0.64
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Data Center Waste Heat Reuse: An Investment Analysis — Aaron P. Wemhoff, Rehan Khalid, et al. · ASME Journal of Engineering for Sustainable Buildings and Cities (2024) | TGRS Research Map | TGRS