Characteristics and Protection Methods for Double-Circuit HVDC Transmission Lines on the Same Tower Considering DC Line-Touching Faults

In heavily loaded regional power grids, some AC transmission lines are confronting escalating pressures due to excessive short-circuit currents. To optimize AC channels, most research advocates for retrofitting existing AC lines into multi-line-commutated converter-based high-voltage direct current (LCC-HVDC) lines. However, there is a contradiction between limited land area for AC stations and the relatively large footprint of passive filters in LCC-HVDC; this paper introduces self-adapted LCC (SLCC) by replacing passive filter groups with a static var generator (SVG). Secondly, the reactive power compensation, harmonic filtering control methods of SVGs, and operation characteristics of the SLCC system are explored, and the harmonics of the grid-side current are reduced by nearly 14.6%. Then, to fill the gap of previous studies on solely AC or AC-DC line touching, inspired by emerging DC line-touching risks in double-circuit (LCC and SLCC) lines on the same tower, the equivalent models are formulated to elucidate the evolution mechanisms of voltage/current and extract fault features in various line-touching faults; it finds that the longitudinal differential current during line-touching faults can be capitalized. Based on the current feature, an effective protection algorithm tailored for the identification of DC line-touching faults is proposed. Finally, simulations are conducted to validate the efficacy of proposed control and protect methods, demonstrating the potential to enhance the reliability of AC to DC conversion projects.

Authors

Institutions

Publication Details

Journal
Electronics
Published
2024-12-13
DOI
https://doi.org/10.3390/electronics13244924
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Characteristics and Protection Methods for Double-Circuit HVDC Transmission Lines on the Same Tower Considering DC Line-Touching Faults

Jinjiao Lin, Yan Tao, Lei Gao, Xiangping Kong et al.
Electronics
HVDC Systems and Fault Protection
article

Characteristics and Protection Methods for Double-Circuit HVDC Transmission Lines on the Same Tower Considering DC Line-Touching Faults

Jinjiao Lin, Yan Tao, Lei Gao, Xiangping Kong, Junchao Zheng, Chenqing Wang
article en

Abstract

In heavily loaded regional power grids, some AC transmission lines are confronting escalating pressures due to excessive short-circuit currents. To optimize AC channels, most research advocates for retrofitting existing AC lines into multi-line-commutated converter-based high-voltage direct current (LCC-HVDC) lines. However, there is a contradiction between limited land area for AC stations and the relatively large footprint of passive filters in LCC-HVDC; this paper introduces self-adapted LCC (SLCC) by replacing passive filter groups with a static var generator (SVG). Secondly, the reactive power compensation, harmonic filtering control methods of SVGs, and operation characteristics of the SLCC system are explored, and the harmonics of the grid-side current are reduced by nearly 14.6%. Then, to fill the gap of previous studies on solely AC or AC-DC line touching, inspired by emerging DC line-touching risks in double-circuit (LCC and SLCC) lines on the same tower, the equivalent models are formulated to elucidate the evolution mechanisms of voltage/current and extract fault features in various line-touching faults; it finds that the longitudinal differential current during line-touching faults can be capitalized. Based on the current feature, an effective protection algorithm tailored for the identification of DC line-touching faults is proposed. Finally, simulations are conducted to validate the efficacy of proposed control and protect methods, demonstrating the potential to enhance the reliability of AC to DC conversion projects.

ElectronicsVol. 13(24)
Shanghai Electric (China) (CN)
State Grid Jiangsu Electric Power
Openalex Percentile: Top 79%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Characteristics and Protection Methods for Double-Circuit HVDC Transmission Lines on the Same Tower Considering DC Line-Touching Faults — Jinjiao Lin, Yan Tao, et al. · Electronics (2024) | TGRS Research Map | TGRS