Study on the Smoke Characteristics of a Cable Fire in an L-Shaped Utility Tunnel under Different Ventilation Conditions

Cable fires frequently occur in utility tunnels, causing incalculable economic losses. In order to reveal the smoke characteristics of an L-shaped utility tunnel cable fire under different ventilation conditions, the temperature distribution, CO concentration, and smoke spread caused by an L-shaped utility tunnel cable fire were numerically simulated. The results show that the air outlet is set on the side of the utility tunnel that is prone to ignition, and the air inlet is set on the side of the utility tunnel far away from the fire source, which is conducive to slowing down the fire temperature and reducing the diffusion rate of CO. The temperature first increases and then decreases along the longitudinal direction of the utility tunnel, taking on a single-hump shape as a whole. However, in Scenarios 4 and 7, the temperature change takes on a double-hump shape. In Scenario 3, the temperature of the utility tunnel decreases with the rise of ventilation speed, and the section that satisfies the safety standard temperature is the longest. With increase in the longitudinal length of the utility tunnel, the CO concentrations in Scenarios 1, 4, and 5 first rise and then drop, while those in Scenarios 2, 3, and 6 decrease gradually. At a ventilation speed of 1.75 m/s in Scenario 3, the CO concentration is controlled the best, and the smoke spread speed takes on a V-shaped variation pattern. Based on three factors, it is concluded that the optimal ventilation mode is a ventilation speed of 1.75 m/s in Scenario 3 (Inlet C and Outlets A and B). By studying different ventilation methods, the most suitable ventilation system for the L-shaped utility tunnel is selected to improve the fire prevention and control capabilities and reduce the loss of personnel and property caused by fire.

Authors

Institutions

Publication Details

Journal
Journal of Pipeline Systems Engineering and Practice
Published
2024-12-10
DOI
https://doi.org/10.1061/jpsea2.pseng-1636
Primary Topic
Fire dynamics and safety research
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Study on the Smoke Characteristics of a Cable Fire in an L-Shaped Utility Tunnel under Different Ventilation Conditions

Lili Hu, M. Xu, Shaohua Liu, Jie Liu et al.
Journal of Pipeline Systems Engineering and Practice
Fire dynamics and safety research
article

Study on the Smoke Characteristics of a Cable Fire in an L-Shaped Utility Tunnel under Different Ventilation Conditions

Lili Hu, M. Xu, Shaohua Liu, Jie Liu, Di Ying
article en

Abstract

Cable fires frequently occur in utility tunnels, causing incalculable economic losses. In order to reveal the smoke characteristics of an L-shaped utility tunnel cable fire under different ventilation conditions, the temperature distribution, CO concentration, and smoke spread caused by an L-shaped utility tunnel cable fire were numerically simulated. The results show that the air outlet is set on the side of the utility tunnel that is prone to ignition, and the air inlet is set on the side of the utility tunnel far away from the fire source, which is conducive to slowing down the fire temperature and reducing the diffusion rate of CO. The temperature first increases and then decreases along the longitudinal direction of the utility tunnel, taking on a single-hump shape as a whole. However, in Scenarios 4 and 7, the temperature change takes on a double-hump shape. In Scenario 3, the temperature of the utility tunnel decreases with the rise of ventilation speed, and the section that satisfies the safety standard temperature is the longest. With increase in the longitudinal length of the utility tunnel, the CO concentrations in Scenarios 1, 4, and 5 first rise and then drop, while those in Scenarios 2, 3, and 6 decrease gradually. At a ventilation speed of 1.75 m/s in Scenario 3, the CO concentration is controlled the best, and the smoke spread speed takes on a V-shaped variation pattern. Based on three factors, it is concluded that the optimal ventilation mode is a ventilation speed of 1.75 m/s in Scenario 3 (Inlet C and Outlets A and B). By studying different ventilation methods, the most suitable ventilation system for the L-shaped utility tunnel is selected to improve the fire prevention and control capabilities and reduce the loss of personnel and property caused by fire.

Journal of Pipeline Systems Engineering and PracticeVol. 16(1)
Qingdao University of Science and Technology (CN), China Shipbuilding Industry Corporation (China) (CN), Development Research Center (CN), Qingdao University of Technology (CN)
Affordable and clean energy
Openalex Percentile: Top 72%
Fire dynamics and safety research
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.