Performance of IBR Power Oscillations Damper according to power system operating conditions

This paper analyses the performance of a Power Oscillations Damping (POD) controller through small-signal stability analysis. The POD is installed in a photovoltaic (PV) power plant controlled in conventional grid-following (GFL) mode. During frequency transients, the POD modifies the reactive power reference of the GFL control, in order to damp electromechanical power system oscillations. The transmission power grid IEEE 9-bus benchmark has been analysed in DIgSILENT PowerFactory software. The PV plant capacity, its location in the network, and the power system operating conditions are considered. Particularly, the analysis of a few specific consumption and generation conditions shows that the electromechanical oscillatory modes of the system are more critical in case of peak load, as it happens for 100 % synchronous generation. The main results are twofold: (i) the significant contribution of the POD to damping electromechanical modes in the scenario of winter evening peak consumption, when the PV plant does not inject active power to the grid, which coincides with the most poorly damped electromechanical modes; and (ii) the lack of negative interaction between PSS and POD controllers.

Authors

Institutions

Publication Details

Published
2024-10-14
DOI
https://doi.org/10.1109/isgteurope62998.2024.10863279
Citations
1
Primary Topic
Power Systems and Renewable Energy
Type
article
Field-Weighted Citation Impact
0.17
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance of IBR Power Oscillations Damper according to power system operating conditions

Raphaël Caire, Thai Phuong, Marta Gomis-Domènech
1 citations
Power Systems and Renewable Energy
0.17
article

Performance of IBR Power Oscillations Damper according to power system operating conditions

Raphaël Caire, Thai Phuong, Marta Gomis-Domènech
article en
1 citations

Abstract

This paper analyses the performance of a Power Oscillations Damping (POD) controller through small-signal stability analysis. The POD is installed in a photovoltaic (PV) power plant controlled in conventional grid-following (GFL) mode. During frequency transients, the POD modifies the reactive power reference of the GFL control, in order to damp electromechanical power system oscillations. The transmission power grid IEEE 9-bus benchmark has been analysed in DIgSILENT PowerFactory software. The PV plant capacity, its location in the network, and the power system operating conditions are considered. Particularly, the analysis of a few specific consumption and generation conditions shows that the electromechanical oscillatory modes of the system are more critical in case of peak load, as it happens for 100 % synchronous generation. The main results are twofold: (i) the significant contribution of the POD to damping electromechanical modes in the scenario of winter evening peak consumption, when the PV plant does not inject active power to the grid, which coincides with the most poorly damped electromechanical modes; and (ii) the lack of negative interaction between PSS and POD controllers.

Institut polytechnique de Grenoble (FR), Centre National de la Recherche Scientifique (FR), Commissariat à l'Énergie Atomique et aux Énergies Alternatives (FR), CEA Grenoble (FR), Université Grenoble Alpes (FR)
Affordable and clean energy
Openalex Percentile: Top 42%
Power Systems and Renewable Energy
0.17
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.