Case Study of Load Shedding Caused by Voltage Sag: Mechanism Analysis and Optimization Measures

Based on an actual fault case in the power grid, this article firstly summarizes and analyzes the network transmission of voltage sag event from high voltage level power grid to low voltage level power grid and the corresponding load reduction. Two categories for the causes for load reduction are summarized, i.e., sensitive equipment shutdown and distribution transformer tripping out. By comparing the operating data with the tolerance curves of computer equipment as well as semiconductor equipment, the reason for shutdown of sensitive equipment is revealed; by analyzing the protective action types of the distribution transformer, the reason for tripping out of distribution transformer is revealed. Then, the impact of under-voltage relay and tripping device is further analyzed. On the basis of the above analysis, the measures to reduce the impact of voltage sag and correspondingly load reduction are put forward from two aspects, i.e., protection configuration and parameter optimization setting, as well as cooperative management between power supply enterprises and important power users.

Authors

Institutions

Publication Details

Published
2024-10-15
DOI
https://doi.org/10.1109/ichqp61174.2024.10768849
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Case Study of Load Shedding Caused by Voltage Sag: Mechanism Analysis and Optimization Measures

Yen-Tsen Liu, Yi Lu, Weijie Cheng, Gong Chen et al.
Power Transformer Diagnostics and Insulation
article

Case Study of Load Shedding Caused by Voltage Sag: Mechanism Analysis and Optimization Measures

Yen-Tsen Liu, Yi Lu, Weijie Cheng, Gong Chen, Zhuo Cheng, Hongxin Li
article en

Abstract

Based on an actual fault case in the power grid, this article firstly summarizes and analyzes the network transmission of voltage sag event from high voltage level power grid to low voltage level power grid and the corresponding load reduction. Two categories for the causes for load reduction are summarized, i.e., sensitive equipment shutdown and distribution transformer tripping out. By comparing the operating data with the tolerance curves of computer equipment as well as semiconductor equipment, the reason for shutdown of sensitive equipment is revealed; by analyzing the protective action types of the distribution transformer, the reason for tripping out of distribution transformer is revealed. Then, the impact of under-voltage relay and tripping device is further analyzed. On the basis of the above analysis, the measures to reduce the impact of voltage sag and correspondingly load reduction are put forward from two aspects, i.e., protection configuration and parameter optimization setting, as well as cooperative management between power supply enterprises and important power users.

Shenzhen Stock Exchange (CN)
Openalex Percentile: Top 80%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.