The Effect on Commutation Failure of Large Capacity HVDC Receiving Terminal With Excitation System of the Flexibility Modification Generator

This paper establishes the excitation structure and model for a flexibility-modified generator and derives the mathematical mechanism for calculating the rotating reactive power of a synchronous generator. By creating a PSCAD simulation environment at the HVDC load center terminal, the corresponding extreme grid potential during an unsuccessful commutation of the HVDC converter station is identified. Using a detailed excitation system model of the synchronous generator within the simulation, the support provided by the flexibility-modified generator's excitation structure during the unsuccessful commutation at the load center is demonstrated.

Authors

Institutions

Publication Details

Published
2024-10-15
DOI
https://doi.org/10.1109/ichqp61174.2024.10768786
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The Effect on Commutation Failure of Large Capacity HVDC Receiving Terminal With Excitation System of the Flexibility Modification Generator

Binxin Yin, Kanjun Zhang, Defu Cai, Gang Han et al.
HVDC Systems and Fault Protection
article

The Effect on Commutation Failure of Large Capacity HVDC Receiving Terminal With Excitation System of the Flexibility Modification Generator

Binxin Yin, Kanjun Zhang, Defu Cai, Gang Han, Fengge Zhang, Tao Wang, Guanqun Sun, Zican Tao, Yu Wang
article en

Abstract

This paper establishes the excitation structure and model for a flexibility-modified generator and derives the mathematical mechanism for calculating the rotating reactive power of a synchronous generator. By creating a PSCAD simulation environment at the HVDC load center terminal, the corresponding extreme grid potential during an unsuccessful commutation of the HVDC converter station is identified. Using a detailed excitation system model of the synchronous generator within the simulation, the support provided by the flexibility-modified generator's excitation structure during the unsuccessful commutation at the load center is demonstrated.

China Three Gorges University (CN), Hubei Water Resources Research Institute (CN), Huazhong University of Science and Technology (CN)
Affordable and clean energy
Openalex Percentile: Top 81%
HVDC Systems and Fault Protection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

The Effect on Commutation Failure of Large Capacity HVDC Receiving Terminal With Excitation System of the Flexibility Modification Generator — Binxin Yin, Kanjun Zhang, et al. · (2024) | TGRS Research Map | TGRS