Experimental measurement of electric field near the insulator string

This paper explores the electric field distribution near a string of six NJ120 high voltage insulators through experimental measurements under various conditions. Using a distributed capacitance method with custom probes connected to an Arduino-based system, tests were conducted on clean and polluted insulators. Pollution was simulated using a tuf-based solution with conductivities ranging from 0.5 to 1.97 mS/cm. Measurements were taken at 13 heights and four distances (1 to1.75 m) under applied AC voltages of 15 to 80 kV. The study also investigates the effects of damaged insulators, placed at different positions (near the high voltage terminal, in the middle, and near the ground), as well as the role of guard rings in improving field uniformity. Results indicate that pollution and damaged insulators significantly increased field intensity, particularly near the high voltage terminal. Guard rings effectively reduced field peaks, with larger radii and optimal placement providing the best performance. These findings contribute to optimizing high voltage insulator design for enhanced reliability.

Authors

Publication Details

Journal
STUDIES IN ENGINEERING AND EXACT SCIENCES
Published
2024-11-29
DOI
https://doi.org/10.54021/seesv5n2-595
Citations
1
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.12
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental measurement of electric field near the insulator string

Benalia M’hamdi, Ali Khechekhouche, Guia Talal, Fettah Khaled et al.
1 citations
STUDIES IN ENGINEERING AND EXACT SCIENCES
High voltage insulation and dielectric phenomena
0.12
article

Experimental measurement of electric field near the insulator string

Benalia M’hamdi, Ali Khechekhouche, Guia Talal, Fettah Khaled, Nedioui Med Abelhamid
article en
1 citations

Abstract

This paper explores the electric field distribution near a string of six NJ120 high voltage insulators through experimental measurements under various conditions. Using a distributed capacitance method with custom probes connected to an Arduino-based system, tests were conducted on clean and polluted insulators. Pollution was simulated using a tuf-based solution with conductivities ranging from 0.5 to 1.97 mS/cm. Measurements were taken at 13 heights and four distances (1 to1.75 m) under applied AC voltages of 15 to 80 kV. The study also investigates the effects of damaged insulators, placed at different positions (near the high voltage terminal, in the middle, and near the ground), as well as the role of guard rings in improving field uniformity. Results indicate that pollution and damaged insulators significantly increased field intensity, particularly near the high voltage terminal. Guard rings effectively reduced field peaks, with larger radii and optimal placement providing the best performance. These findings contribute to optimizing high voltage insulator design for enhanced reliability.

STUDIES IN ENGINEERING AND EXACT SCIENCESVol. 5(2)
Openalex Percentile: Top 58%
High voltage insulation and dielectric phenomena
0.12
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.