A Study on Estimation of Insulation Resistance in Low-Voltage Direct Current Systems Using Open-Type Midpoint Grounding System
In low-voltage DC systems, the grounding system is mainly a two-wire or three-wire IT system. Among them, the IT high-resistance midpoint grounding system has advantages in detecting 1-wire ground fault, but has disadvantages in continuous loss and insulation resistance measurement. This paper proposes a method to estimate the insulation resistance of the + and - lines using the measured voltage when the switch of the high-resistance midpoint is closed/opened in the open-type midpoint grounding system. Through the proposed method, it prevents continuous losses due to high-resistance midpoint grounding and allows the insulation resistance to be estimated through switch control when the measured voltage exceeds a certain value. The proposed method was verified by simulation using MATALB/SIMULINK and experiment.
Authors
- Jeong-Chay Jeon (ORCID: https://orcid.org/0000-0002-6414-3057)
- Ki-Yeon Lee (ORCID: https://orcid.org/0000-0003-1867-3273)
- Chan-Hyeok Oh (ORCID: https://orcid.org/0000-0003-4323-124X)
- Seung-Taek Lim
Publication Details
- Journal
- The Transactions of The Korean Institute of Electrical Engineers
- Published
- 2024-11-28
- DOI
- https://doi.org/10.5370/kiee.2024.73.11.2091
- Primary Topic
- Engineering Applied Research
- Type
- article
- Field-Weighted Citation Impact
- 0.00