Small-Signal Stability of Grid-Forming Converters Under Fault Conditions

The threshold virtual impedance (TVI) method is gaining significant research interest for limiting current in grid-forming (GFM) converters under fault conditions. This method is valued for its ability to maintain voltage source behavior during such faults. However, sequence extraction and negative-sequence control (NSC) are often overlooked in small-signal stability assessments under these conditions. This paper develops a small-signal impedance model for GFM converters based on the TVI current limitation method during fault conditions. Using developed small-signal impedance model, the impact of NSC on system stability during faults is analyzed. Additionally, key TVI parameters, such as the low-pass filter (LPF) cutoff frequency and the impedance ratio X/R are examined. The findings suggest that NSC, a lower LPF cutoff frequency, and a lower X/R ratio enhance system stability under fault conditions. However, a lower cutoff frequency may not effectively limit fault currents, and a lower X/R ratio can lead to reduced voltage magnitude during faults. Time-domain simulations validate these analytical results.

Authors

Institutions

Publication Details

Published
2024-11-06
DOI
https://doi.org/10.1109/scems63294.2024.10756384
Primary Topic
High-Voltage Power Transmission Systems
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Small-Signal Stability of Grid-Forming Converters Under Fault Conditions

Qianchao Liao, Lie Xu, Yinyu Chen, Xianxian Zhao et al.
High-Voltage Power Transmission Systems
article

Small-Signal Stability of Grid-Forming Converters Under Fault Conditions

Qianchao Liao, Lie Xu, Yinyu Chen, Xianxian Zhao, Xia Chen, Yin Chen
article en

Abstract

The threshold virtual impedance (TVI) method is gaining significant research interest for limiting current in grid-forming (GFM) converters under fault conditions. This method is valued for its ability to maintain voltage source behavior during such faults. However, sequence extraction and negative-sequence control (NSC) are often overlooked in small-signal stability assessments under these conditions. This paper develops a small-signal impedance model for GFM converters based on the TVI current limitation method during fault conditions. Using developed small-signal impedance model, the impact of NSC on system stability during faults is analyzed. Additionally, key TVI parameters, such as the low-pass filter (LPF) cutoff frequency and the impedance ratio X/R are examined. The findings suggest that NSC, a lower LPF cutoff frequency, and a lower X/R ratio enhance system stability under fault conditions. However, a lower cutoff frequency may not effectively limit fault currents, and a lower X/R ratio can lead to reduced voltage magnitude during faults. Time-domain simulations validate these analytical results.

University College Dublin (IE), University of Strathclyde (GB), Huazhong University of Science and Technology (CN), Southwest Jiaotong University (CN)
National Natural Science Foundation of China, National Key Research and Development Program of China
Climate action
Openalex Percentile: Top 81%
High-Voltage Power Transmission Systems
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.