High Voltage Power Transformer Protection Parameters Calculation and Differential Protection Testing using a Three Phase Test Kit

The paper sets out the main protection functions used in substations for protecting power transformers as well as the parameters calculation for some of them. The case study will refer to a $400 / 110 \mathrm{kV}$ substation equipped with mobile cells in external GIS technology, in order to supply the 110 kV voltage of an industrial platform with a maximum power demand estimated at 270 MVA. In addition to the technical and economical criteria, the degree of safety in the supply of electricity users was considered a criterion of great importance in the process of developing the presented solutions. The calculation was made for differential protection as well as for distance protection and in addition to the actual calculation, the logic for determining the thresholds is presented. As the transformer differential protection is the main protection function, it was tested using a three phase testing kit to ensure proper functionality.

Authors

Institutions

Publication Details

Published
2024-10-17
DOI
https://doi.org/10.1109/epei63510.2024.10758155
Primary Topic
Power Systems Fault Detection
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

High Voltage Power Transformer Protection Parameters Calculation and Differential Protection Testing using a Three Phase Test Kit

Sorina Costinaș, Mircea Augustin Roşca, Ovidiu Emanuel Chiriţescu
Power Systems Fault Detection
article

High Voltage Power Transformer Protection Parameters Calculation and Differential Protection Testing using a Three Phase Test Kit

Sorina Costinaș, Mircea Augustin Roşca, Ovidiu Emanuel Chiriţescu
article en

Abstract

The paper sets out the main protection functions used in substations for protecting power transformers as well as the parameters calculation for some of them. The case study will refer to a $400 / 110 \mathrm{kV}$ substation equipped with mobile cells in external GIS technology, in order to supply the 110 kV voltage of an industrial platform with a maximum power demand estimated at 270 MVA. In addition to the technical and economical criteria, the degree of safety in the supply of electricity users was considered a criterion of great importance in the process of developing the presented solutions. The calculation was made for differential protection as well as for distance protection and in addition to the actual calculation, the logic for determining the thresholds is presented. As the transformer differential protection is the main protection function, it was tested using a three phase testing kit to ensure proper functionality.

Universitatea Națională de Știință și Tehnologie Politehnica București (RO)
Affordable and clean energy
Openalex Percentile: Top 75%
Power Systems Fault Detection
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.