Analysis of Simulated Partial Discharge Waveform and Converter Noise for the Partial Discharge Diagnosis in HVDC MI Submarine Cable

This Partial discharge diagnosis in HVDC (High Voltage Direct Current) MI (Mass Impregnated) submarine cables is very difficult due to the attenuation of partial discharge signals in magnitude and frequency during the propagation through long-distance line. Nevertheless, since partial discharge signals are large and wide due to the degradation characteristics of MI cable insulation compared with XLPE (Cross-linked polyethylene) cable systems, propagated partial discharge signals may be detected if measured in a low frequency band. However, partial discharge measurement becomes very complicated and difficult due to noise in the converter station. In this study, noise characteristics were analyzed by measuring conversion noise, and the propagated characteristics of the partial discharge signal generated in a distant location were analyzed using EMTP (Electro Magnetic Transient Program) with the experiment for the model. By comparing these simulated partial discharge signals with noise signals measured in the converter station, the possibility of partial discharge diagnosis of HVDC MI submarine cables was examined.

Authors

Institutions

Publication Details

Published
2024-08-04
DOI
https://doi.org/10.1109/icpadm61663.2024.10750683
Citations
3
Primary Topic
High voltage insulation and dielectric phenomena
Type
article
Field-Weighted Citation Impact
0.35
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of Simulated Partial Discharge Waveform and Converter Noise for the Partial Discharge Diagnosis in HVDC MI Submarine Cable

Chanyeong Lee, You-Sun Won, Jeong‐Tae Kim
3 citations
High voltage insulation and dielectric phenomena
0.35
article

Analysis of Simulated Partial Discharge Waveform and Converter Noise for the Partial Discharge Diagnosis in HVDC MI Submarine Cable

Chanyeong Lee, You-Sun Won, Jeong‐Tae Kim
article en
3 citations

Abstract

This Partial discharge diagnosis in HVDC (High Voltage Direct Current) MI (Mass Impregnated) submarine cables is very difficult due to the attenuation of partial discharge signals in magnitude and frequency during the propagation through long-distance line. Nevertheless, since partial discharge signals are large and wide due to the degradation characteristics of MI cable insulation compared with XLPE (Cross-linked polyethylene) cable systems, propagated partial discharge signals may be detected if measured in a low frequency band. However, partial discharge measurement becomes very complicated and difficult due to noise in the converter station. In this study, noise characteristics were analyzed by measuring conversion noise, and the propagated characteristics of the partial discharge signal generated in a distant location were analyzed using EMTP (Electro Magnetic Transient Program) with the experiment for the model. By comparing these simulated partial discharge signals with noise signals measured in the converter station, the possibility of partial discharge diagnosis of HVDC MI submarine cables was examined.

Daejin University (KR)
Openalex Percentile: Top 43%
High voltage insulation and dielectric phenomena
0.35
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.