Transient and Steady-State Evaluation of Distributed Generation in Medium-Voltage Distribution Networks

As power generation systems with increasingly higher capacities are interconnected with distribution networks, a pressing need arises for a thorough analysis of their integration and the subsequent impacts on medium-voltage lines. This study conducts a comprehensive evaluation, encompassing both steady-state and transient behaviours, leading to a holistic assessment of a real-world biogas generation system integrated into a medium-voltage network. Although the methodology does not introduce revolutionary concepts, its detailed application on a real feeder under various operating conditions adds practical value to the existing body of knowledge. The methodology explores various aspects, including voltage profiles, load capacity, power losses, short-circuit currents, and protection coordination in steady-state conditions. Additionally, a transient analysis is performed to examine the system’s response under fault conditions. This systematic approach provides a deep understanding of the system’s behaviour across diverse operational scenarios, enriching the field with practical insights. The key contributions of this study include identifying the effects of distributed generation systems (DGSs) on short-circuit currents, protection coordination, and defining voltage levels that briefly exceed the CBEMA quality curve. The benefits of incorporating a generation system into a distribution network are discussed from various technical perspectives. In a peak demand scenario, with a 1.72 MW generation capacity, the phase current experiences a notable reduction of 35.78%. Concurrently, the minimum peak demand voltage increases from 12.62 to 12.83 kV compared to a nominal voltage of 12.7 kV. Furthermore, the contribution of the generation system to the short-circuit current remains minimal, staying below 4% even under the most adverse conditions. However, our findings reveal that voltage levels exceed the upper limit of the CBEMA quality curve briefly during a single-phase fault with generation, which could potentially damage electronic equipment connected to the grid. Nonetheless, the likelihood of encountering a single-phase grounding fault with zero resistance remains low.

Authors

Institutions

Publication Details

Journal
Energies
Published
2024-11-20
DOI
https://doi.org/10.3390/en17225783
Citations
2
Primary Topic
Islanding Detection in Power Systems
Type
article
Field-Weighted Citation Impact
0.42
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Transient and Steady-State Evaluation of Distributed Generation in Medium-Voltage Distribution Networks

Jean‐Michel Clairand, Xavier Serrano‐Guerrero, Antonio Barragán-Escandón, Daniel Guillén-López
2 citations
Energies
Islanding Detection in Power Systems
0.42
article

Transient and Steady-State Evaluation of Distributed Generation in Medium-Voltage Distribution Networks

Jean‐Michel Clairand, Xavier Serrano‐Guerrero, Antonio Barragán-Escandón, Daniel Guillén-López
article en
2 citations

Abstract

As power generation systems with increasingly higher capacities are interconnected with distribution networks, a pressing need arises for a thorough analysis of their integration and the subsequent impacts on medium-voltage lines. This study conducts a comprehensive evaluation, encompassing both steady-state and transient behaviours, leading to a holistic assessment of a real-world biogas generation system integrated into a medium-voltage network. Although the methodology does not introduce revolutionary concepts, its detailed application on a real feeder under various operating conditions adds practical value to the existing body of knowledge. The methodology explores various aspects, including voltage profiles, load capacity, power losses, short-circuit currents, and protection coordination in steady-state conditions. Additionally, a transient analysis is performed to examine the system’s response under fault conditions. This systematic approach provides a deep understanding of the system’s behaviour across diverse operational scenarios, enriching the field with practical insights. The key contributions of this study include identifying the effects of distributed generation systems (DGSs) on short-circuit currents, protection coordination, and defining voltage levels that briefly exceed the CBEMA quality curve. The benefits of incorporating a generation system into a distribution network are discussed from various technical perspectives. In a peak demand scenario, with a 1.72 MW generation capacity, the phase current experiences a notable reduction of 35.78%. Concurrently, the minimum peak demand voltage increases from 12.62 to 12.83 kV compared to a nominal voltage of 12.7 kV. Furthermore, the contribution of the generation system to the short-circuit current remains minimal, staying below 4% even under the most adverse conditions. However, our findings reveal that voltage levels exceed the upper limit of the CBEMA quality curve briefly during a single-phase fault with generation, which could potentially damage electronic equipment connected to the grid. Nonetheless, the likelihood of encountering a single-phase grounding fault with zero resistance remains low.

EnergiesVol. 17(22)
Politecnica Salesiana University (EC), Universidad de Las Américas (EC)
Affordable and clean energy
Openalex Percentile: Top 36%
Islanding Detection in Power Systems
0.42
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.