An approach to improve grounding resistance characteristic in existing 115 KV transmission towers

• The study operates in two modes: actual observation and simulation. Several 115 kV transmission systems of EGAT were observed, while simulations were conducted using the ATPDraw program. • The performance of the proposed method was validated by comparing actual and simulation observations. • This study considers the effects of complex variables such as impedance resistance, which were not considered in previous studies. Effective grounding can attenuate fault currents and reduce damage to power system equipment, making the grounding system a crucial protection scheme. Generally, the ground resistance is set to a value less than 10 Ω. However, in practice, it is difficult to achieve this in certain areas, such as mountains, plains, and swamps. To address this problem, this study analyses the (1) actual footing resistance, (2) ground resistivity, and (3) ground length of transmission towers located in specific areas. Non-linear factors, impedance, and coupling effect are considered instead of traditional variables. A grounding design algorithm is proposed based on the ATPDraw program. Simulation results are applied to the 115 kV real-world system of the Electricity Generating Authority of Thailand. The grounding system exhibits a satisfactory performance improvement, as evidenced by comparisons between simulation and actual measurements. The findings are useful for implementing future improvements in grounding protection schemes.

Authors

Institutions

Publication Details

Journal
Results in Engineering
Published
2024-11-20
DOI
https://doi.org/10.1016/j.rineng.2024.103465
Citations
5
Primary Topic
Lightning and Electromagnetic Phenomena
Type
article
Field-Weighted Citation Impact
1.66
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An approach to improve grounding resistance characteristic in existing 115 KV transmission towers

Sulee Bunjongjit, Wiwat Kulwongwit, Chaichan Pothisarn, Praikanok Lertwanitrot et al.
5 citations
Results in Engineering
Lightning and Electromagnetic Phenomena
1.66
article

An approach to improve grounding resistance characteristic in existing 115 KV transmission towers

Sulee Bunjongjit, Wiwat Kulwongwit, Chaichan Pothisarn, Praikanok Lertwanitrot, Atthapol Ngaopitakkul
article en
5 citations

Abstract

• The study operates in two modes: actual observation and simulation. Several 115 kV transmission systems of EGAT were observed, while simulations were conducted using the ATPDraw program. • The performance of the proposed method was validated by comparing actual and simulation observations. • This study considers the effects of complex variables such as impedance resistance, which were not considered in previous studies. Effective grounding can attenuate fault currents and reduce damage to power system equipment, making the grounding system a crucial protection scheme. Generally, the ground resistance is set to a value less than 10 Ω. However, in practice, it is difficult to achieve this in certain areas, such as mountains, plains, and swamps. To address this problem, this study analyses the (1) actual footing resistance, (2) ground resistivity, and (3) ground length of transmission towers located in specific areas. Non-linear factors, impedance, and coupling effect are considered instead of traditional variables. A grounding design algorithm is proposed based on the ATPDraw program. Simulation results are applied to the 115 kV real-world system of the Electricity Generating Authority of Thailand. The grounding system exhibits a satisfactory performance improvement, as evidenced by comparisons between simulation and actual measurements. The findings are useful for implementing future improvements in grounding protection schemes.

Results in EngineeringVol. 24
Electricity Generating Authority of Thailand (TH), Rajamangala University of Technology Rattanakosin (TH), Thai Dietetic Association (TH), King Mongkut's Institute of Technology Ladkrabang (TH)
Affordable and clean energy
Openalex Percentile: Top 16%
Lightning and Electromagnetic Phenomena
1.66
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.