Energy consumption analysis of building air-conditioning systems using centrifugal compressor with gas bearing under annual operating conditions

The water chiller using centrifugal compressor with gas bearing is an important development direction for building energy saving, but the additional refrigerant cycle for bearing and motor colling leads to more complex performance especially under the various operating condition. Based on the heating and cooling loads of a building in Nanjing and the local climate conditions, this paper innovatively establishes an air conditioning system model using centrifugal compressor with gas bearings (CCGB), and analyzes the performance of air-cooling and water-cooling methods. Considering the heating and cooling loads, the annual energy consumption of two systems was compared consider the climate condition. The results show that the COP of water-cooling system is larger than that of air-cooling system due to the better heat transfer condition. The larger power consumption of compressor for air-cooling system leads to the larger motor cooling load. The cooling methods have obvious influence on the vapor-injected mass flow rate, but have small impact on the mass flow rate of motor cooling and bearing gas supply. The energy efficiency of air-cooling and water-cooling system in summer are 3.77 and 5.12 respectively, and the total energy consumption in the whole year are 32.4 tons and 33.5 tons of standard coal. The mathematical model of air-conditioning system using centrifugal compressor with gas bearing (CCGB) is built, and the performance using air and water-cooling system is analyzed based on the annual climate conditions in Nanjing. For the whole refrigeration season, the water-cooling system have higher energy efficiency, but the air-cooling system is more efficient for the heating season due to the added heat from the heat pump. Although the air-cooling system consumes more energy in summer, the annual energy consumption is only slightly lower than that of the water-cooling system. The energy consumption in winter is higher than that in summer for both of the air and water-cooling systems, and they consume 32.4 and 33.5 tons of standard coal throughout the year, respectively.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2024-11-19
DOI
https://doi.org/10.1016/j.csite.2024.105522
Citations
9
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
1.91

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Energy consumption analysis of building air-conditioning systems using centrifugal compressor with gas bearing under annual operating conditions

J.S. Wang, Yuanyang Zhao, Qichao Yang, Zilong Wang et al.
9 citations
Case Studies in Thermal Engineering
Refrigeration and Air Conditioning Technologies
1.91
article

Energy consumption analysis of building air-conditioning systems using centrifugal compressor with gas bearing under annual operating conditions

J.S. Wang, Yuanyang Zhao, Qichao Yang, Zilong Wang, Yuandong Li, Liansheng Li, Guangbin Liu, Y L Zuo
article en
9 citations

Abstract

The water chiller using centrifugal compressor with gas bearing is an important development direction for building energy saving, but the additional refrigerant cycle for bearing and motor colling leads to more complex performance especially under the various operating condition. Based on the heating and cooling loads of a building in Nanjing and the local climate conditions, this paper innovatively establishes an air conditioning system model using centrifugal compressor with gas bearings (CCGB), and analyzes the performance of air-cooling and water-cooling methods. Considering the heating and cooling loads, the annual energy consumption of two systems was compared consider the climate condition. The results show that the COP of water-cooling system is larger than that of air-cooling system due to the better heat transfer condition. The larger power consumption of compressor for air-cooling system leads to the larger motor cooling load. The cooling methods have obvious influence on the vapor-injected mass flow rate, but have small impact on the mass flow rate of motor cooling and bearing gas supply. The energy efficiency of air-cooling and water-cooling system in summer are 3.77 and 5.12 respectively, and the total energy consumption in the whole year are 32.4 tons and 33.5 tons of standard coal. The mathematical model of air-conditioning system using centrifugal compressor with gas bearing (CCGB) is built, and the performance using air and water-cooling system is analyzed based on the annual climate conditions in Nanjing. For the whole refrigeration season, the water-cooling system have higher energy efficiency, but the air-cooling system is more efficient for the heating season due to the added heat from the heat pump. Although the air-cooling system consumes more energy in summer, the annual energy consumption is only slightly lower than that of the water-cooling system. The energy consumption in winter is higher than that in summer for both of the air and water-cooling systems, and they consume 32.4 and 33.5 tons of standard coal throughout the year, respectively.

Case Studies in Thermal EngineeringVol. 64
Qingdao University of Science and Technology (CN), Cryogenic Industries (United States) (US)
National Natural Science Foundation of China
Affordable and clean energy
Openalex Percentile: Top 15%
Refrigeration and Air Conditioning Technologies
1.91
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.