Study on the influence of fire source location on cable tunnel detection and alarm system

In order to study the fire detection method of cable tunnel. We carried out physical experiments in the cable tunnel test section, using the heater pyrolyze PVC so that its pyrolysis as the ignition source obtained a total of 17 fire source location points in the horizontal and vertical directions of seven different fire detectors, and only processed the response time data of the alarm detector obtained the response time and the analysis results were drawn. With the increase of the distance from the fire source, the response time of each type of detector increases in different forms. It is found that the detection distance of the grating fiber temperature sensor is shorter, and the response time near the fire source is more stable. The detection performance of the point pyrolytic particle detector is more affected by the detection distance, which is advantageous for the detection point to have better response performance. The intelligent active suction detector is also affected by the detection distance, which is less affected than the point detector, the response time curve is more stable, and the detection performance is better at each test point. X Document Identification Code; A.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2024-11-19
DOI
https://doi.org/10.1016/j.csite.2024.105507
Citations
1
Primary Topic
Fire Detection and Safety Systems
Type
article
Field-Weighted Citation Impact
0.36
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Study on the influence of fire source location on cable tunnel detection and alarm system

Zihao Liang, Zeyu Wang, Lei Lei
1 citations
Case Studies in Thermal Engineering
Fire Detection and Safety Systems
0.36
article

Study on the influence of fire source location on cable tunnel detection and alarm system

Zihao Liang, Zeyu Wang, Lei Lei
article en
1 citations

Abstract

In order to study the fire detection method of cable tunnel. We carried out physical experiments in the cable tunnel test section, using the heater pyrolyze PVC so that its pyrolysis as the ignition source obtained a total of 17 fire source location points in the horizontal and vertical directions of seven different fire detectors, and only processed the response time data of the alarm detector obtained the response time and the analysis results were drawn. With the increase of the distance from the fire source, the response time of each type of detector increases in different forms. It is found that the detection distance of the grating fiber temperature sensor is shorter, and the response time near the fire source is more stable. The detection performance of the point pyrolytic particle detector is more affected by the detection distance, which is advantageous for the detection point to have better response performance. The intelligent active suction detector is also affected by the detection distance, which is less affected than the point detector, the response time curve is more stable, and the detection performance is better at each test point. X Document Identification Code; A.

Case Studies in Thermal EngineeringVol. 64
University of Science and Technology of China (CN), People’s Hospital of Rizhao (CN), China People's Police University (CN)
Openalex Percentile: Top 38%
Fire Detection and Safety Systems
0.36
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.