Energy-Efficiency-Oriented Spatial Configuration of VRV Outdoor Units in an Equipment Layer Under Background Wind Conditions

This study provides a spatial configuration method to improve the cooling efficiency of multiple VRV outdoor units placed on equipment layers with high floors. Relevant factors include wind parameters, the placement of multiple outdoor units, and louver. A total of 96 cases were designed. CFD simulations were used to obtain the inlet air temperature distributions of multiple outdoor units and then calculate their cooling efficiency. The results found that these factors have effects on the average cooling efficiency of outdoor units in a single row to a certain extent. The influencing degrees of these factors, from large to small, were the louver angle, wind parameters, and the placement of multiple outdoor units. When the cooling efficiency of outdoor units was maximum and the louver angle was 15°, the louvers could be oriented perpendicular to the dominant wind direction (90°) when wind speed was ≥6 m/s, and the unit spacing was 600 mm. Based on this, when the number of outdoor units was expanded in the limited space, staggered arrangements with different directions of heat exchange surfaces were a recommended optimization layout. This study provides technical support for improving the working efficiency of VRV outdoor units in an equipment layer.

Authors

Institutions

Publication Details

Journal
Buildings
Published
2024-11-19
DOI
https://doi.org/10.3390/buildings14113681
Primary Topic
Wind and Air Flow Studies
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Energy-Efficiency-Oriented Spatial Configuration of VRV Outdoor Units in an Equipment Layer Under Background Wind Conditions

Xiaoyu Tian, Lin Liu, Haoran Huang
Buildings
Wind and Air Flow Studies
article

Energy-Efficiency-Oriented Spatial Configuration of VRV Outdoor Units in an Equipment Layer Under Background Wind Conditions

Xiaoyu Tian, Lin Liu, Haoran Huang
article en

Abstract

This study provides a spatial configuration method to improve the cooling efficiency of multiple VRV outdoor units placed on equipment layers with high floors. Relevant factors include wind parameters, the placement of multiple outdoor units, and louver. A total of 96 cases were designed. CFD simulations were used to obtain the inlet air temperature distributions of multiple outdoor units and then calculate their cooling efficiency. The results found that these factors have effects on the average cooling efficiency of outdoor units in a single row to a certain extent. The influencing degrees of these factors, from large to small, were the louver angle, wind parameters, and the placement of multiple outdoor units. When the cooling efficiency of outdoor units was maximum and the louver angle was 15°, the louvers could be oriented perpendicular to the dominant wind direction (90°) when wind speed was ≥6 m/s, and the unit spacing was 600 mm. Based on this, when the number of outdoor units was expanded in the limited space, staggered arrangements with different directions of heat exchange surfaces were a recommended optimization layout. This study provides technical support for improving the working efficiency of VRV outdoor units in an equipment layer.

BuildingsVol. 14(11)
Guangdong University of Technology (CN)
National Natural Science Foundation of China
Affordable and clean energy
Openalex Percentile: Top 82%
Wind and Air Flow Studies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.