Optimization of Substation Grounding System Design on T-Shape Through Computer Simulation Approach

The grounding system is a safety system for electrical equipment failures, circuit disturbances caused by lightning strikes, and short circuit faults to the ground that can conduct to the human body. This study aims to optimize the design of the grounding system at substations with a T-shape grid and compare the cost efficiency required. The method used involves modifying the grid shape and adjusting the number of conductors on each axis of the T-shape grid design, as well as adding rod conductors. The touch voltage tolerance of the grounding system at the Substation of Electric Company in Pekanbaru is 737.6 V for a 50 kg body and 998.4 V for a 70 kg body, with a step voltage tolerance of 2458.2 V for a 50 kg body and 3327.1 V for a 70 kg body. The more economical design is the combination of the T-shape grid-rod with 8 conductors on the x-axis and 20 conductors on the y-axis, totaling 1345 meters in length, along with the addition of ground rods. The cost for this design is approximately IDR 315,587,250, which is lower than the design that only uses a grid with 10 conductors on the x-axis and 23 conductors on the y-axis, totaling 1,600 meters in length, costing IDR 373,200,000.

Authors

Institutions

Publication Details

Published
2024-10-16
DOI
https://doi.org/10.1109/iconeei64414.2024.10748078
Citations
1
Primary Topic
Power Systems and Technologies
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Optimization of Substation Grounding System Design on T-Shape Through Computer Simulation Approach

Iswadi Hasyim Rosma, Suwitno, Amir Hamzah, Fri Murdiya et al.
1 citations
Power Systems and Technologies
0.21
article

Optimization of Substation Grounding System Design on T-Shape Through Computer Simulation Approach

Iswadi Hasyim Rosma, Suwitno, Amir Hamzah, Fri Murdiya, Firdaus Firdaus, Azizil Kurnia, Dimas Abyan
article en
1 citations

Abstract

The grounding system is a safety system for electrical equipment failures, circuit disturbances caused by lightning strikes, and short circuit faults to the ground that can conduct to the human body. This study aims to optimize the design of the grounding system at substations with a T-shape grid and compare the cost efficiency required. The method used involves modifying the grid shape and adjusting the number of conductors on each axis of the T-shape grid design, as well as adding rod conductors. The touch voltage tolerance of the grounding system at the Substation of Electric Company in Pekanbaru is 737.6 V for a 50 kg body and 998.4 V for a 70 kg body, with a step voltage tolerance of 2458.2 V for a 50 kg body and 3327.1 V for a 70 kg body. The more economical design is the combination of the T-shape grid-rod with 8 conductors on the x-axis and 20 conductors on the y-axis, totaling 1345 meters in length, along with the addition of ground rods. The cost for this design is approximately IDR 315,587,250, which is lower than the design that only uses a grid with 10 conductors on the x-axis and 23 conductors on the y-axis, totaling 1,600 meters in length, costing IDR 373,200,000.

Riau University (ID)
Openalex Percentile: Top 46%
Power Systems and Technologies
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Optimization of Substation Grounding System Design on T-Shape Through Computer Simulation Approach — Iswadi Hasyim Rosma, Suwitno, et al. · (2024) | TGRS Research Map | TGRS