An experimental investigation on the role of the operating time of the mist device on the thermal performances of a water-sprayed air-cooled condenser and on the energy consumption of the cooling system

• Water misting upstream of an air-cooled condenser allows to intensify heat transfers • The role of maintaining misting for a longer time on heat dissipation is investigated • An increase of 54.9% in the COP of the cooling system for two minutes of misting • 17.2% reduction in energy consumption of the cooling system • Heat transfer destruction and health risks associated to water misting can be avoided Water spraying upstream of an air-cooled condenser enables high heat dissipation. Meanwhile, a good control on the spray-heater parameters is crucial to avoid excesses of water and heat transfer destruction. This paper aims to experimentally illustrate the impact of the operating time of the mist device on the condenser thermal performances and the refrigerator energy consumption. To better visualize water stagnation phenomena, experiments are performed using a low pressure spraying device with 0.0065 L/min in water flow rate and 2-4 bar in pressure range. Several series of measurements have been performed on the refrigerant temperatures and pressures and on power consumption for different operating times of the mist device. Measured results showed that with 2 min of misting, the condenser inlet airflow and the refrigerant condensing pressure drop respectively from 32 to 27.4°C and 10 to 7.2 bar, while for 1 min of misting they decrease from 32 to 28°C and 10 to 7.6 bar, respectively. In this work, compared to the system without misting, maintaining the mist system in operation for 2 min allowed 54.9% enhancement in the Coefficient of Performance and 17.2% reduction in energy consumption. Consequently, the operating time of the mist device highly affects the condenser cooling performances and the refrigerator power consumption. Meanwhile, it is found that, above 2 min of misting, the condenser inlet airflow is saturated and the condensing pressure hardly changes while water stagnation is occurring. Hence, misting should be applied momentarily to avoid heat transfer destruction and water losses.

Authors

Institutions

Publication Details

Journal
International Journal of Thermofluids
Published
2024-11-01
DOI
https://doi.org/10.1016/j.ijft.2024.100956
Citations
4
Primary Topic
Adsorption and Cooling Systems
Type
article
Field-Weighted Citation Impact
0.85
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

An experimental investigation on the role of the operating time of the mist device on the thermal performances of a water-sprayed air-cooled condenser and on the energy consumption of the cooling system

Biram Dieng, Ibra Bop
4 citations
International Journal of Thermofluids
Adsorption and Cooling Systems
0.85
article

An experimental investigation on the role of the operating time of the mist device on the thermal performances of a water-sprayed air-cooled condenser and on the energy consumption of the cooling system

Biram Dieng, Ibra Bop
article en
4 citations

Abstract

• Water misting upstream of an air-cooled condenser allows to intensify heat transfers • The role of maintaining misting for a longer time on heat dissipation is investigated • An increase of 54.9% in the COP of the cooling system for two minutes of misting • 17.2% reduction in energy consumption of the cooling system • Heat transfer destruction and health risks associated to water misting can be avoided Water spraying upstream of an air-cooled condenser enables high heat dissipation. Meanwhile, a good control on the spray-heater parameters is crucial to avoid excesses of water and heat transfer destruction. This paper aims to experimentally illustrate the impact of the operating time of the mist device on the condenser thermal performances and the refrigerator energy consumption. To better visualize water stagnation phenomena, experiments are performed using a low pressure spraying device with 0.0065 L/min in water flow rate and 2-4 bar in pressure range. Several series of measurements have been performed on the refrigerant temperatures and pressures and on power consumption for different operating times of the mist device. Measured results showed that with 2 min of misting, the condenser inlet airflow and the refrigerant condensing pressure drop respectively from 32 to 27.4°C and 10 to 7.2 bar, while for 1 min of misting they decrease from 32 to 28°C and 10 to 7.6 bar, respectively. In this work, compared to the system without misting, maintaining the mist system in operation for 2 min allowed 54.9% enhancement in the Coefficient of Performance and 17.2% reduction in energy consumption. Consequently, the operating time of the mist device highly affects the condenser cooling performances and the refrigerator power consumption. Meanwhile, it is found that, above 2 min of misting, the condenser inlet airflow is saturated and the condensing pressure hardly changes while water stagnation is occurring. Hence, misting should be applied momentarily to avoid heat transfer destruction and water losses.

International Journal of ThermofluidsVol. 24
Université Alioune Diop de Bambey (SN)
Affordable and clean energy
Openalex Percentile: Top 30%
Adsorption and Cooling Systems
0.85
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.