An Experimental Study on Behavior of Power Conditioning System for Photovoltaic Power Generation System Connected to End of Distribution Line
ABSTRACT Reverse power flow from a photovoltaic (PV) power generation system to distribution system is limited below a certain limit value. The behavior of a power conditioning system (PCS) for large capacity PV power generation system when the output power approached the output power limit value was experimentally estimated. Under the condition, the PCS became uncontrollable. It was pointed out that this phenomenon was caused by the maximum power point tracking (MPPT) control of the PCS. Furthermore, some methods to avoid the uncontrollable condition of PCS were shown.
Authors
- Ippei Matsuura
- Hirotaka Shimizu
- Mayu Yamaguchi
- Hiroki Yamanaka
Institutions
- The Polytechnic University of Japan (JP)
Publication Details
- Journal
- Electrical Engineering in Japan
- Published
- 2024-11-06
- DOI
- https://doi.org/10.1002/eej.23481
- Primary Topic
- Power Systems and Renewable Energy
- Type
- article
- Field-Weighted Citation Impact
- 0.00