Water Quality Analysis of a 300 Mvar Large-Scale Dual Internal Water Cooling Synchronous Condenser External Cooling System and Exploration of Optimal Water Treatment Agent Dosage at Different Temperatures

The external cooling water system of a 300 Mvar dual internal water cooling synchronous condenser at a certain ultra-high voltage converter station continued to exhibit significant scaling and corrosion, even with regular addition of scale and corrosion inhibitors. To solve this problem, the external cooling water of the synchronous condenser was sampled and tested periodically, with the main test items including conductivity, pH value, turbidity, hardness, alkalinity, and other water quality parameters directly related to corrosion and scaling. The trends of these parameters over time were also analyzed. The results showed that as the operation time increased, the cooling water became concentrated during multiple circulation cycles, and the various dissolved or suspended substances underwent a certain degree of enrichment. However, the addition of scale and corrosion inhibitors did not dynamically adjust according to the changes in water quality, and there was always an excessive dosage. Thus, using the external cooling water as the experimental sample, static scale inhibition tests and rotating coupon corrosion tests were conducted to evaluate the scale and corrosion inhibition performance of the commercial AS-582 scale and corrosion inhibitor used at this ultra-high voltage converter station under different conditions. Considering the more obvious corrosive tendency of this water sample, the focus was on testing its corrosion inhibition performance. When the dosage was 600 ppm, the scale inhibition effect was optimal, with an inhibition rate of 92.15%. The corrosion inhibition effect of this scale and the corrosion inhibitor were significantly related to water temperature. At 25 °C, when the dosage was 500 ppm, the corrosion inhibition effect was optimal, with an inhibition rate of 86.79%. However, when the temperature increased to 40 °C, the corrosion inhibition effect under each dosage was significantly worse, unable to meet the requirements, and the use of other corrosion inhibitors in combination was necessary. This work will provide a reference for the scientific use of scale and corrosion inhibitors.

Authors

Institutions

Publication Details

Journal
Water
Published
2024-11-05
DOI
https://doi.org/10.3390/w16223158
Citations
1
Primary Topic
Solar-Powered Water Purification Methods
Type
article
Field-Weighted Citation Impact
0.10

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Water Quality Analysis of a 300 Mvar Large-Scale Dual Internal Water Cooling Synchronous Condenser External Cooling System and Exploration of Optimal Water Treatment Agent Dosage at Different Temperatures

Junjie Zhang, Yuquan Wu, Yuxiang Gao, Qiaozhen Ji et al.
1 citations
Water
Solar-Powered Water Purification Methods
0.10
article

Water Quality Analysis of a 300 Mvar Large-Scale Dual Internal Water Cooling Synchronous Condenser External Cooling System and Exploration of Optimal Water Treatment Agent Dosage at Different Temperatures

Junjie Zhang, Yuquan Wu, Yuxiang Gao, Qiaozhen Ji, Hongbiao Dong, Zhikui Liu, Zhongkang Zhou, Peipei Fan, Xiaohong Gu, Xiaoqiong Guo, Wu Yan, Xiaochun Chen, Yunqing Xu, Lin Yang, Xiaowei Ma
article en
1 citations

Abstract

The external cooling water system of a 300 Mvar dual internal water cooling synchronous condenser at a certain ultra-high voltage converter station continued to exhibit significant scaling and corrosion, even with regular addition of scale and corrosion inhibitors. To solve this problem, the external cooling water of the synchronous condenser was sampled and tested periodically, with the main test items including conductivity, pH value, turbidity, hardness, alkalinity, and other water quality parameters directly related to corrosion and scaling. The trends of these parameters over time were also analyzed. The results showed that as the operation time increased, the cooling water became concentrated during multiple circulation cycles, and the various dissolved or suspended substances underwent a certain degree of enrichment. However, the addition of scale and corrosion inhibitors did not dynamically adjust according to the changes in water quality, and there was always an excessive dosage. Thus, using the external cooling water as the experimental sample, static scale inhibition tests and rotating coupon corrosion tests were conducted to evaluate the scale and corrosion inhibition performance of the commercial AS-582 scale and corrosion inhibitor used at this ultra-high voltage converter station under different conditions. Considering the more obvious corrosive tendency of this water sample, the focus was on testing its corrosion inhibition performance. When the dosage was 600 ppm, the scale inhibition effect was optimal, with an inhibition rate of 92.15%. The corrosion inhibition effect of this scale and the corrosion inhibitor were significantly related to water temperature. At 25 °C, when the dosage was 500 ppm, the corrosion inhibition effect was optimal, with an inhibition rate of 86.79%. However, when the temperature increased to 40 °C, the corrosion inhibition effect under each dosage was significantly worse, unable to meet the requirements, and the use of other corrosion inhibitors in combination was necessary. This work will provide a reference for the scientific use of scale and corrosion inhibitors.

WaterVol. 16(22)
Tianjin University (CN), State Grid Corporation of China (China) (CN)
Electric Power Research Institute
Clean water and sanitation
Openalex Percentile: Top 64%
Solar-Powered Water Purification Methods
0.10
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.