Evaluating ATP testing for distribution system monitoring: comparison to HPC, impact of chlorine quenching, and hold time dependency

Adenosine triphosphate (ATP) assays have a faster turnaround time and higher sensitivity than traditional cultivation methods for microbial monitoring. Challenges implementing ATP testing include incompatibility with chlorine quenching agents and hold time sensitivity, which are not well-studied. Chlorinated distribution system samples were collected from two Canadian utilities, Metro Vancouver (n = 40 samples) and Halifax Water (n = 283). No significant correlations were observed between heterotrophic cell count (HPC) and cellular ATP, suggesting these do not correlate well in waters with low biological activity (median HPC < 2 CFU/mL). However, interpretation of HPC and cATP results (based on the HPC guideline of 100 CFU/mL and cATP of 10 pg/mL) yielded the same conclusion for 95% of samples, suggesting a potential decision-making framework to replace HPC with cATP. Moreover, cATP correlates better with free chlorine (p < 0.04) compared with HPC for one of the studied systems. Importantly, adding chlorine quench (10% sodium thiosulfate) did not produce significantly different cATP results, nor did analyzing at various hold times of 4-, 6-, and 24-h. This study supports the integration of ATP testing into existing sampling procedures for water utilities, as a sensitive, fast, and reliable monitoring method.

Authors

Institutions

Publication Details

Journal
Journal of Biological Engineering
Published
2024-11-05
DOI
https://doi.org/10.1186/s13036-024-00446-z
Citations
1
Primary Topic
Water Treatment and Disinfection
Type
article
Field-Weighted Citation Impact
0.31
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluating ATP testing for distribution system monitoring: comparison to HPC, impact of chlorine quenching, and hold time dependency

Madjid Mohseni, Leili Abkar, William S. Chen
1 citations
Journal of Biological Engineering
Water Treatment and Disinfection
0.31
article

Evaluating ATP testing for distribution system monitoring: comparison to HPC, impact of chlorine quenching, and hold time dependency

Madjid Mohseni, Leili Abkar, William S. Chen
article en
1 citations

Abstract

Adenosine triphosphate (ATP) assays have a faster turnaround time and higher sensitivity than traditional cultivation methods for microbial monitoring. Challenges implementing ATP testing include incompatibility with chlorine quenching agents and hold time sensitivity, which are not well-studied. Chlorinated distribution system samples were collected from two Canadian utilities, Metro Vancouver (n = 40 samples) and Halifax Water (n = 283). No significant correlations were observed between heterotrophic cell count (HPC) and cellular ATP, suggesting these do not correlate well in waters with low biological activity (median HPC < 2 CFU/mL). However, interpretation of HPC and cATP results (based on the HPC guideline of 100 CFU/mL and cATP of 10 pg/mL) yielded the same conclusion for 95% of samples, suggesting a potential decision-making framework to replace HPC with cATP. Moreover, cATP correlates better with free chlorine (p < 0.04) compared with HPC for one of the studied systems. Importantly, adding chlorine quench (10% sodium thiosulfate) did not produce significantly different cATP results, nor did analyzing at various hold times of 4-, 6-, and 24-h. This study supports the integration of ATP testing into existing sampling procedures for water utilities, as a sensitive, fast, and reliable monitoring method.

Journal of Biological EngineeringVol. 18(1)
University of British Columbia Hospital (CA), University of British Columbia (CA)
Clean water and sanitation
Openalex Percentile: Top 36%
Water Treatment and Disinfection
0.31
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Evaluating ATP testing for distribution system monitoring: comparison to HPC, impact of chlorine quenching, and hold time dependency — Madjid Mohseni, Leili Abkar, et al. · Journal of Biological Engineering (2024) | TGRS Research Map | TGRS