Ensuring Stable Operation of Wind Farms Connected to Distribution Networks

Wind farms with type IV wind turbines from various manufacturers are being massively put into operation. These wind turbines comply with the requirements of the grid codes of the countries where they are designed and/or manufactured, but do not factor in the specific features of the distribution networks of other countries to which they are connected. The study at issue involves a comparative analysis of the requirements of grid codes of different countries for the stable operation of wind turbines under standard disturbances. The low voltage ride through (LVRT) characteristic makes it possible to prevent wind turbine shutdowns in case of short-term voltage dips of a given depth and duration. The calculations of transient processes indicate that wind turbines may not meet the requirements of the grid code of a particular country for their stable operation. As a result, standard disturbances will block the reactive current injection and the wind turbine will be switched off. This is often caused by the relay protection devices with a time delay of 1–2 s, which are used in distribution networks and implement the functions of long-range redundancy. Excessive shutdowns of wind turbines lead to emergency rises in the loads for the generating units of conventional power plants, aggravating the post-accident conditions and disconnecting consumers of electricity. This article presents a method for checking the LVRT characteristic settings for compliance with the technical requirements for wind turbines. To prevent wind turbine outages, one should either change the configuration of the LVRT characteristic, upgrade the relay protection devices in the distribution network adjacent to the wind farm, or implement group or individual technical solutions at the wind farm. The performance of the proposed technical solutions is confirmed by the calculations of transient processes.

Authors

Institutions

Publication Details

Journal
Applied Sciences
Published
2024-10-26
DOI
https://doi.org/10.3390/app14219794
Citations
4
Primary Topic
Wind Turbine Control Systems
Type
article
Field-Weighted Citation Impact
0.83

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Ensuring Stable Operation of Wind Farms Connected to Distribution Networks

Konstantin Suslov, Pavel V. ILYUSHIN, Aleksandr Simonov, Sergey Filippov
4 citations
Applied Sciences
Wind Turbine Control Systems
0.83
article

Ensuring Stable Operation of Wind Farms Connected to Distribution Networks

Konstantin Suslov, Pavel V. ILYUSHIN, Aleksandr Simonov, Sergey Filippov
article en
4 citations

Abstract

Wind farms with type IV wind turbines from various manufacturers are being massively put into operation. These wind turbines comply with the requirements of the grid codes of the countries where they are designed and/or manufactured, but do not factor in the specific features of the distribution networks of other countries to which they are connected. The study at issue involves a comparative analysis of the requirements of grid codes of different countries for the stable operation of wind turbines under standard disturbances. The low voltage ride through (LVRT) characteristic makes it possible to prevent wind turbine shutdowns in case of short-term voltage dips of a given depth and duration. The calculations of transient processes indicate that wind turbines may not meet the requirements of the grid code of a particular country for their stable operation. As a result, standard disturbances will block the reactive current injection and the wind turbine will be switched off. This is often caused by the relay protection devices with a time delay of 1–2 s, which are used in distribution networks and implement the functions of long-range redundancy. Excessive shutdowns of wind turbines lead to emergency rises in the loads for the generating units of conventional power plants, aggravating the post-accident conditions and disconnecting consumers of electricity. This article presents a method for checking the LVRT characteristic settings for compliance with the technical requirements for wind turbines. To prevent wind turbine outages, one should either change the configuration of the LVRT characteristic, upgrade the relay protection devices in the distribution network adjacent to the wind farm, or implement group or individual technical solutions at the wind farm. The performance of the proposed technical solutions is confirmed by the calculations of transient processes.

Applied SciencesVol. 14(21)
Russian Academy of Sciences (RU), Moscow Power Engineering Institute (RU), Energy Research Institute (RU), Irkutsk National Research Technical University (RU)
Russian Science Foundation, Russian Academy of Sciences
Affordable and clean energy
Openalex Percentile: Top 26%
Wind Turbine Control Systems
0.83
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.