A portable VNA-based system for grid impedance measurements
Conducted emissions are strongly dependent on the grid and EUT impedance, to measure in live conditions. A portable system based on a low-cost VNA and two internal or external current probes is presented. It was verified in the lab against various calibration standards $(50 \Omega$, mismatched termination, $150 \Omega$ coupling-decoupling network and 100 pF capacitor) using a Agilent E5061B as reference. Results of calibration and the effects of probes non-linearity are provided, having considered both saturation (with an external bias circuit) and signal-to-noise ratio (by injecting external noise). The maximum observed spread of impedance magnitude is $\mathbf{1 \%}$ for matched condition ($50 \Omega$) and 10% in mismatched conditions. Performance can always be improved by using a more expensive and bulkier VNA.
Authors
- Andrea Mariscotti (ORCID: https://orcid.org/0000-0002-0096-7305)
- M. Wojciechowski
- Serdar Büyük
- Osman Şen (ORCID: https://orcid.org/0000-0002-5716-3316)
- K. Štibernik
Institutions
- Slovenian Institute of Quality and Metrology (SI)
- Tübitak National Metrology Institute (TR)
- Central Office of Measures (PL)
- University of Genoa (IT)
Publication Details
- Published
- 2024-09-02
- DOI
- https://doi.org/10.1109/emceurope59828.2024.10722179
- Citations
- 4
- Primary Topic
- Energy Harvesting in Wireless Networks
- Type
- article
- Field-Weighted Citation Impact
- 0.83
Funders
- HORIZON EUROPE Framework Programme