Optimization of Unbalanced Protection for AC Filter Capacitor Bank in UHV Converter Station

Taking the unbalanced protection action of the AC filter group at Changji converter station as the research object, this paper introduces the common structure and unbalanced protection principle of C1 capacitor, sorts out the handling and troubleshooting measures when the capacitor group fails, and verifies the consistency between the current unbalanced protection setting and logic and the initial design. In response to the problem of one or a small number of capacitor components failure within a single capacitor unit leading to the tripping of the entire capacitor group, the reasons for the deviation between the actual operating voltage and the design voltage, as well as the deviation between the power frequency current melting time and the tripping time of section III protection, resulting in insufficient internal fuse energy and ineffective melting, were identified. A set value and logic optimization method for capacitor group imbalance protection were proposed. The effectiveness of the proposed method was verified through PSCAD/EMTDC simulation modeling, avoiding frequent tripping of AC filter banks and improving equipment availability.

Authors

Institutions

Publication Details

Published
2024-08-08
DOI
https://doi.org/10.1109/hvdc62448.2024.10723075
Citations
1
Primary Topic
High-Voltage Power Transmission Systems
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Optimization of Unbalanced Protection for AC Filter Capacitor Bank in UHV Converter Station

Chuanbao Xun, Yinzhang Peng, Wenxin Li, Qi Li et al.
1 citations
High-Voltage Power Transmission Systems
0.21
article

Optimization of Unbalanced Protection for AC Filter Capacitor Bank in UHV Converter Station

Chuanbao Xun, Yinzhang Peng, Wenxin Li, Qi Li, Jincheng Jiang, Xiang Wang
article en
1 citations

Abstract

Taking the unbalanced protection action of the AC filter group at Changji converter station as the research object, this paper introduces the common structure and unbalanced protection principle of C1 capacitor, sorts out the handling and troubleshooting measures when the capacitor group fails, and verifies the consistency between the current unbalanced protection setting and logic and the initial design. In response to the problem of one or a small number of capacitor components failure within a single capacitor unit leading to the tripping of the entire capacitor group, the reasons for the deviation between the actual operating voltage and the design voltage, as well as the deviation between the power frequency current melting time and the tripping time of section III protection, resulting in insufficient internal fuse energy and ineffective melting, were identified. A set value and logic optimization method for capacitor group imbalance protection were proposed. The effectiveness of the proposed method was verified through PSCAD/EMTDC simulation modeling, avoiding frequent tripping of AC filter banks and improving equipment availability.

Inner Mongolia Electric Power (China) (CN)
Affordable and clean energy
Openalex Percentile: Top 47%
High-Voltage Power Transmission Systems
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.