Influence of Thermal Energy Storage Integration Strategy on System Performance and Refrigerant Charge for Small-Scale R290 Heat Pumps

As small-scale (2.5 – 5 kW) heat pumps across the US increase straining the grid during peak hours, integrated heat pump thermal energy storage (HP-TES) systems can assist by load shifting. However, challenges arise when assembling these systems, as direct refrigerant-phase change material (PCM) heat exchangers (HXs) increase refrigerant charge, and indirect secondary loops degrade HP-TES performance. In this work, direct and indirect HP-TES configurations were sized using commercially available HXs to compare the available load shift time and performance at similar refrigerant charges. For the same indirect 5 kW HP-TES refrigerant charge, directly HP-TES can operate up to 72 and 145 minutes in cooling and heating modes, respectively, using small diameter tubes. Using Modelica, COP increases for direct and indirect HP-TES were 22% and 9%, respectively, given the parasitic losses in the indirect HP-TES. Overall, small-scale direct HP-TES can have comparable refrigerant charges with indirect HP-TES maximizing COP improvements.

Authors

Institutions

Publication Details

Journal
OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information)
Published
2024-10-09
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Influence of Thermal Energy Storage Integration Strategy on System Performance and Refrigerant Charge for Small-Scale R290 Heat Pumps

Mohamed I. A. Othman
OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information)
Refrigeration and Air Conditioning Technologies
article

Influence of Thermal Energy Storage Integration Strategy on System Performance and Refrigerant Charge for Small-Scale R290 Heat Pumps

Mohamed I. A. Othman
article en

Abstract

As small-scale (2.5 – 5 kW) heat pumps across the US increase straining the grid during peak hours, integrated heat pump thermal energy storage (HP-TES) systems can assist by load shifting. However, challenges arise when assembling these systems, as direct refrigerant-phase change material (PCM) heat exchangers (HXs) increase refrigerant charge, and indirect secondary loops degrade HP-TES performance. In this work, direct and indirect HP-TES configurations were sized using commercially available HXs to compare the available load shift time and performance at similar refrigerant charges. For the same indirect 5 kW HP-TES refrigerant charge, directly HP-TES can operate up to 72 and 145 minutes in cooling and heating modes, respectively, using small diameter tubes. Using Modelica, COP increases for direct and indirect HP-TES were 22% and 9%, respectively, given the parasitic losses in the indirect HP-TES. Overall, small-scale direct HP-TES can have comparable refrigerant charges with indirect HP-TES maximizing COP improvements.

OSTI OAI (U.S. Department of Energy Office of Scientific and Technical Information)
University of Maryland, College Park (US)
U.S. Department of Energy, Office of Energy Efficiency and Renewable Energy, Office of Energy Efficiency
Affordable and clean energy
Refrigeration and Air Conditioning Technologies
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.