Voltages in Disconnected Overhead Transmission Line, Induced by Electric and Magnetic Field of Operated Transmission Line

The paper proposes the algorithm for calculation of voltages in phases and wire of parallel disconnected overhead transmission line induced by electric and magnetic field of operating in coordinated load mode overhead transmission line. Two single-circuit 220 kV lines were taken as the studied ones. Disconnected line protected phase and part length in which this phase should be protected (1 km) are selected. This section is grounded by the ends to line towers. Disconnected line all other phases and lightning wires are grounded to one tower inside the protected area. Electric field effects determine by capacitive currents in grounding phases, wires, grounding devices and in the ground. Magnetic field effects determine by current in the circuit of protected phase and the generated in phases and wires part grounded by one side s longitudinal electromotive force. Equations for voltage distribution over the ground along each phase and wire in the protected and non-protected areas finding are compiled according to electric and magnetic impact schemes. Resulting voltage distribution along each part determine by received voltages electrical and magnetic components adding.

Authors

Publication Details

Published
2024-09-27
DOI
https://doi.org/10.1109/uralcon62137.2024.10718999
Citations
1
Primary Topic
Electromagnetic Launch and Propulsion Technology
Type
article
Field-Weighted Citation Impact
1.30
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Voltages in Disconnected Overhead Transmission Line, Induced by Electric and Magnetic Field of Operated Transmission Line

D. O. Demchenko, Rubtsova Nb, Andrey Tokarskskiy
1 citations
Electromagnetic Launch and Propulsion Technology
1.30
article

Voltages in Disconnected Overhead Transmission Line, Induced by Electric and Magnetic Field of Operated Transmission Line

D. O. Demchenko, Rubtsova Nb, Andrey Tokarskskiy
article en
1 citations

Abstract

The paper proposes the algorithm for calculation of voltages in phases and wire of parallel disconnected overhead transmission line induced by electric and magnetic field of operating in coordinated load mode overhead transmission line. Two single-circuit 220 kV lines were taken as the studied ones. Disconnected line protected phase and part length in which this phase should be protected (1 km) are selected. This section is grounded by the ends to line towers. Disconnected line all other phases and lightning wires are grounded to one tower inside the protected area. Electric field effects determine by capacitive currents in grounding phases, wires, grounding devices and in the ground. Magnetic field effects determine by current in the circuit of protected phase and the generated in phases and wires part grounded by one side s longitudinal electromotive force. Equations for voltage distribution over the ground along each phase and wire in the protected and non-protected areas finding are compiled according to electric and magnetic impact schemes. Resulting voltage distribution along each part determine by received voltages electrical and magnetic components adding.

Affordable and clean energy
Openalex Percentile: Top 12%
Electromagnetic Launch and Propulsion Technology
1.30
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Voltages in Disconnected Overhead Transmission Line, Induced by Electric and Magnetic Field of Operated Transmission Line — D. O. Demchenko, Rubtsova Nb, et al. · (2024) | TGRS Research Map | TGRS