Analysis of the CO2 + C2Cl4 mixture in high temperature heat pumps: Experimental thermal stability, liquid densities and cycle simulations

• The CO 2 + C 2 Cl 4 mixture is introduced as innovative working fluid for heat pumps. • High efficiency is possible for heat pumps with sensible heat sinks and heat sources. • Experimental thermal stability results proved the feasibility of reaching 250 °C. • Experimental densities of the mixture allowed for a more detailed thermodynamic model. • Calculations on spray dryer heat pump show higher performance compared to pure fluids. Transcritical heat pumps working with CO 2 -based mixtures with a low-volatility dopant are found to achieve good performances in thermally integrated heat pumps, especially when sensible heat sources and heat sinks are considered. This paper introduces in literature tetrachloroethylene, C 2 Cl 4 , as CO 2 -dopant for the mixture to be adopted as working fluid in high temperature heat pumps. To calibrate the thermodynamic model used in the cycle simulations, an experimental characterization on the mixture is proposed: liquid densities of the mixtures are measured, in a wide range of concentration, optimizing the binary interaction parameter of the Peng Robinson equation of state. Moreover, the thermal stability of pure C 2 Cl 4 is experimentally evaluated, identifying the maximum allowable compressor outlet temperature between 200 °C and 250 °C, with a decomposition rate below 1 %/year if the fluid is kept at temperatures around 200 °C. Then, the potentialities of this very high temperature heat pump are assessed in spray dryer applications: a coefficient of performance around 3.38 is obtained for a conventional spray dryer plant, corresponding to 73 % of second law efficiency, considering an air flow heated from ambient temperature to 200 °C as the sink, while cooling the sensible heat source, available at 76 °C, below 30 °C. As term of comparison, the same system adopting propane, instead of the CO 2 + C 2 Cl 4 mixture, would achieve a coefficient of performance and second law efficiency of 2.94 and 64 %, respectively.

Authors

Institutions

Publication Details

Journal
Energy Conversion and Management
Published
2024-10-17
DOI
https://doi.org/10.1016/j.enconman.2024.119145
Citations
4
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.85

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Analysis of the CO2 + C2Cl4 mixture in high temperature heat pumps: Experimental thermal stability, liquid densities and cycle simulations

Michele Doninelli, Giampaolo Manzolini, Ettore Morosini, Paolo Stringari et al.
4 citations
Energy Conversion and Management
Refrigeration and Air Conditioning Technologies
0.85
article

Analysis of the CO2 + C2Cl4 mixture in high temperature heat pumps: Experimental thermal stability, liquid densities and cycle simulations

Michele Doninelli, Giampaolo Manzolini, Ettore Morosini, Paolo Stringari, Gioele Di Marcoberardino, Paolo Iora, Mauro Riva
article en
4 citations

Abstract

• The CO 2 + C 2 Cl 4 mixture is introduced as innovative working fluid for heat pumps. • High efficiency is possible for heat pumps with sensible heat sinks and heat sources. • Experimental thermal stability results proved the feasibility of reaching 250 °C. • Experimental densities of the mixture allowed for a more detailed thermodynamic model. • Calculations on spray dryer heat pump show higher performance compared to pure fluids. Transcritical heat pumps working with CO 2 -based mixtures with a low-volatility dopant are found to achieve good performances in thermally integrated heat pumps, especially when sensible heat sources and heat sinks are considered. This paper introduces in literature tetrachloroethylene, C 2 Cl 4 , as CO 2 -dopant for the mixture to be adopted as working fluid in high temperature heat pumps. To calibrate the thermodynamic model used in the cycle simulations, an experimental characterization on the mixture is proposed: liquid densities of the mixtures are measured, in a wide range of concentration, optimizing the binary interaction parameter of the Peng Robinson equation of state. Moreover, the thermal stability of pure C 2 Cl 4 is experimentally evaluated, identifying the maximum allowable compressor outlet temperature between 200 °C and 250 °C, with a decomposition rate below 1 %/year if the fluid is kept at temperatures around 200 °C. Then, the potentialities of this very high temperature heat pump are assessed in spray dryer applications: a coefficient of performance around 3.38 is obtained for a conventional spray dryer plant, corresponding to 73 % of second law efficiency, considering an air flow heated from ambient temperature to 200 °C as the sink, while cooling the sensible heat source, available at 76 °C, below 30 °C. As term of comparison, the same system adopting propane, instead of the CO 2 + C 2 Cl 4 mixture, would achieve a coefficient of performance and second law efficiency of 2.94 and 64 %, respectively.

Energy Conversion and ManagementVol. 322
Université Paris Sciences et Lettres (FR), University of Brescia (IT), Politecnico di Milano (IT)
European Commission
Affordable and clean energy
Openalex Percentile: Top 30%
Refrigeration and Air Conditioning Technologies
0.85
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.