Experimental comparison of cycle modifications and ejector control methods using variable geometry and CO2 pump in a multi-evaporator transcritical CO2 refrigeration system
• Four CO 2 cycles were experimentally compared over four ambient conditions. • A variable-diameter nozzle and liquid CO 2 pump were assessed as ejector control methods. • The pump operated stably and was able to increase the ejector efficiency by 15 %. • Ejector and IHX cycles increased COP by 4.64 % and 9.47 %, respectively. To reduce the direct global warming impact of refrigerants in HVAC&R applications, low-global warming potential (GWP) refrigerants, including natural refrigerants, have been extensively investigated as alternatives to hydrofluorocarbon (HFC) refrigerants. Among the natural refrigerants, Carbon Dioxide (CO 2 ) offers several advantages, such as excellent transport and thermo-physical properties, being neither toxic nor flammable, and having a low price and high availability around the world. However, the high critical pressure and low critical temperature of CO 2 often lead to transcritical operation, resulting in lower efficiency due to the additional compressor power necessary to achieve transcritical operation relative to subcritical HFC cycles. Therefore, a number of cycle modifications are used to enhance the coefficient of performance (COP) of transcritical CO 2 cycles to meet or surpass those of HFC cycles. This paper provides a systematic experimental investigation of four such cycle architectures by employing the same multi-stage, two-evaporator CO 2 refrigeration cycle test stand, 3 of these configurations in transcritical and 1 in subcritical conditions. The four cycles architectures included intercooling, open economization, an internal heat exchanger and two different ejector control approaches. Specifically, a variable-diameter motive nozzle and a variable-speed liquid CO 2 pump located directly upstream of the ejector motive nozzle inlet were analyzed. Based on the experimental data, the maximum COP improvements are 4.64 % and 9.47 % when the ejector and the internal heat exchanger are used, respectively. The CO 2 pump, once successfully stabilized, can control the ejector, increase its efficiency by up to 15 % and increase the cooling capacity to a maximum of 6.2 %. Nevertheless, a reduction in COP is measured when the pump is in use; however, unlike the other three different configurations, it was only analyzed under subcritical conditions.
Authors
- Gabriele Toffoletti (ORCID: https://orcid.org/0000-0002-6924-5183)
- Eckhard A. Groll (ORCID: https://orcid.org/0000-0002-1034-7089)
- Riley B. Barta (ORCID: https://orcid.org/0000-0002-8833-7411)
- Davide Ziviani (ORCID: https://orcid.org/0000-0002-1778-445X)
- Haotian Liu (ORCID: https://orcid.org/0000-0002-7887-5144)
- Steven M. Grajales
Institutions
- University of Udine (IT)
- Purdue University West Lafayette (US)
Publication Details
- Journal
- International Journal of Refrigeration
- Published
- 2024-10-16
- DOI
- https://doi.org/10.1016/j.ijrefrig.2024.10.001
- Citations
- 8
- Primary Topic
- Refrigeration and Air Conditioning Technologies
- Type
- article
- Field-Weighted Citation Impact
- 1.70