The Wear Resistance of the SF6 Circuit Breaker Contact System Composite Materials when Clearing Short-Circuit Currents

The article presents the results of experiments on studying the switching wear resistance of the composite materials used in the contact system of 35 kV SF6 circuit breakers during repeated clearing of short-circuit currents of up to 20 kA. Two versions of arc electrodes were considered: when using tungsten-copper (W-Cu) metal-ceramic composite materials with powder components and when using W-Cu electrode materials reinforced with tungsten fibers. For the arc electrodes made on the basis of tungsten-nickel-copper (W-Cu) metal-ceramic composite materials with powder components forming a tungsten-nickel frame impregnated with copper, two cases of components were studied: with a tungsten content of up to 70 and up to 50%. According to the study results, a composite with a tungsten content of 70% was chosen as the recommended one. For tungsten-copper electrode materials reinforced with tungsten fibers, predominant wear of the central part of their working surface and the concentration of the arc basic spot on it were found, which result in that the wear of the fluoroplastic nozzle is by 30-40% lower compared with its wear in the case of using W-Cu electrodes with powder components.

Authors

Publication Details

Journal
Elektrichestvo
Published
2024-08-16
DOI
https://doi.org/10.24160/0013-5380-2024-8-42-49
Citations
1
Primary Topic
Electrical Contact Performance and Analysis
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

The Wear Resistance of the SF6 Circuit Breaker Contact System Composite Materials when Clearing Short-Circuit Currents

В. Т. Чемерис
1 citations
Elektrichestvo
Electrical Contact Performance and Analysis
0.21
article

The Wear Resistance of the SF6 Circuit Breaker Contact System Composite Materials when Clearing Short-Circuit Currents

В. Т. Чемерис
article en
1 citations

Abstract

The article presents the results of experiments on studying the switching wear resistance of the composite materials used in the contact system of 35 kV SF6 circuit breakers during repeated clearing of short-circuit currents of up to 20 kA. Two versions of arc electrodes were considered: when using tungsten-copper (W-Cu) metal-ceramic composite materials with powder components and when using W-Cu electrode materials reinforced with tungsten fibers. For the arc electrodes made on the basis of tungsten-nickel-copper (W-Cu) metal-ceramic composite materials with powder components forming a tungsten-nickel frame impregnated with copper, two cases of components were studied: with a tungsten content of up to 70 and up to 50%. According to the study results, a composite with a tungsten content of 70% was chosen as the recommended one. For tungsten-copper electrode materials reinforced with tungsten fibers, predominant wear of the central part of their working surface and the concentration of the arc basic spot on it were found, which result in that the wear of the fluoroplastic nozzle is by 30-40% lower compared with its wear in the case of using W-Cu electrodes with powder components.

Elektrichestvo(8)
Openalex Percentile: Top 51%
Electrical Contact Performance and Analysis
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.