Enhancing Semiconductor Chiller Performance: Investigating the Performance Characteristics of Ultra-Low-Temperature Chillers Applying a Liquid Receiver

This study investigates the implementation of a cryogenic chiller utilizing a mixed-refrigerant cascade refrigeration cycle (MRCRC). In this setup, R-404A is employed in the high-temperature circuit (HTC), while a mixture of refrigerants is utilized in the low-temperature circuit (LTC). Unlike a conventional MRCRC that operates without a receiver to maintain the composition ratio, this research explores the impact of receiver installation on system performance. Experiments were conducted with and without a receiver to assess performance improvements and device behavior. With a fixed refrigerant charge of 4 kg, the suction and discharge pressures of the LTC compressor remained low and stable after the receiver’s installation. The addition of a receiver significantly reduced the cooling time, with further reductions observed as the refrigerant charge increased. The system achieved evaporative heat capacities of 0.59, 1.76, and 2 kW for refrigerant charges of 4, 7, and 9 kg, respectively. Notably, at the maximum refrigerant charge of 11 kg, the evaporative heat capacity peaked at 3.3 kW. These findings indicate that incorporating a receiver is crucial for enhancing the cooling performance of cryogenic coolers using mixed refrigerants and stabilizing device operation. This contrasts with previous studies that omitted receivers due to concerns over potential alterations in the composition ratio of the mixed refrigerant.

Authors

Institutions

Publication Details

Journal
Energies
Published
2024-10-16
DOI
https://doi.org/10.3390/en17205144
Citations
1
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.21

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Enhancing Semiconductor Chiller Performance: Investigating the Performance Characteristics of Ultra-Low-Temperature Chillers Applying a Liquid Receiver

H. Jung, Chang-Hyo Son, Joon-Hyuk Lee, S.J. Lee
1 citations
Energies
Refrigeration and Air Conditioning Technologies
0.21
article

Enhancing Semiconductor Chiller Performance: Investigating the Performance Characteristics of Ultra-Low-Temperature Chillers Applying a Liquid Receiver

H. Jung, Chang-Hyo Son, Joon-Hyuk Lee, S.J. Lee
article en
1 citations

Abstract

This study investigates the implementation of a cryogenic chiller utilizing a mixed-refrigerant cascade refrigeration cycle (MRCRC). In this setup, R-404A is employed in the high-temperature circuit (HTC), while a mixture of refrigerants is utilized in the low-temperature circuit (LTC). Unlike a conventional MRCRC that operates without a receiver to maintain the composition ratio, this research explores the impact of receiver installation on system performance. Experiments were conducted with and without a receiver to assess performance improvements and device behavior. With a fixed refrigerant charge of 4 kg, the suction and discharge pressures of the LTC compressor remained low and stable after the receiver’s installation. The addition of a receiver significantly reduced the cooling time, with further reductions observed as the refrigerant charge increased. The system achieved evaporative heat capacities of 0.59, 1.76, and 2 kW for refrigerant charges of 4, 7, and 9 kg, respectively. Notably, at the maximum refrigerant charge of 11 kg, the evaporative heat capacity peaked at 3.3 kW. These findings indicate that incorporating a receiver is crucial for enhancing the cooling performance of cryogenic coolers using mixed refrigerants and stabilizing device operation. This contrasts with previous studies that omitted receivers due to concerns over potential alterations in the composition ratio of the mixed refrigerant.

EnergiesVol. 17(20)
Pukyong National University (KR)
Ministry of Trade, Industry and Energy, Korea Institute of Energy Technology Evaluation and Planning
Affordable and clean energy
Openalex Percentile: Top 51%
Refrigeration and Air Conditioning Technologies
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.

Enhancing Semiconductor Chiller Performance: Investigating the Performance Characteristics of Ultra-Low-Temperature Chillers Applying a Liquid Receiver — H. Jung, Chang-Hyo Son, et al. · Energies (2024) | TGRS Research Map | TGRS