Hybrid Power Synchronization Based Transient Stability Enhanced Control for Grid-Forming Inverters Under Symmetrical Grid Fault

The current limiter can effectively limit the overcurrent for grid forming (GFM) inverter, but it also makes the inverter easier to lose the stable equilibrium point (SEP) during grid fault. The untimely fault clearing, inaccurate fault depth detection and grid impedance measurement result may lead to overoptimistic deceleration effect evaluation and transient instability problem. In this article, the hybrid power synchronization method is proposed to increase the robustness in transient stability of the GFM inverter against parameters variation. The reactive power that internally related to fault depth is introduced as the dynamic active power reference. It can make sure that the SEP exist during grid fault without the need of fault depth detection. In the same time, the dynamic power compensation related to fault depth is also achieved. The reactive power feedback gain optimization and equivalent power reference limitation method are further given to increase the robustness against large impedance measurement error. Based on equal area criterion, it is demonstrated that with the proposed hybrid power synchronization method, the transient stability of GFM voltage source converter always can be guaranteed once the SEP exists. The impact of line-to-ground fault on transient stability is analyzed and the robust enhanced method is also given. Finally, the effectiveness of the proposed method is verified on a 5 kW experimental platform.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Power Electronics
Published
2024-10-14
DOI
https://doi.org/10.1109/tpel.2024.3479325
Citations
15
Primary Topic
Power Systems and Renewable Energy
Type
article
Field-Weighted Citation Impact
2.54
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Hybrid Power Synchronization Based Transient Stability Enhanced Control for Grid-Forming Inverters Under Symmetrical Grid Fault

Xiaoming Zha, Pengfei Sun, Zhen Tian, Xiping Ma et al.
15 citations
IEEE Transactions on Power Electronics
Power Systems and Renewable Energy
2.54
article

Hybrid Power Synchronization Based Transient Stability Enhanced Control for Grid-Forming Inverters Under Symmetrical Grid Fault

Xiaoming Zha, Pengfei Sun, Zhen Tian, Xiping Ma, Meng Huang, Yibin Tao, Chong Shao
article en
15 citations

Abstract

The current limiter can effectively limit the overcurrent for grid forming (GFM) inverter, but it also makes the inverter easier to lose the stable equilibrium point (SEP) during grid fault. The untimely fault clearing, inaccurate fault depth detection and grid impedance measurement result may lead to overoptimistic deceleration effect evaluation and transient instability problem. In this article, the hybrid power synchronization method is proposed to increase the robustness in transient stability of the GFM inverter against parameters variation. The reactive power that internally related to fault depth is introduced as the dynamic active power reference. It can make sure that the SEP exist during grid fault without the need of fault depth detection. In the same time, the dynamic power compensation related to fault depth is also achieved. The reactive power feedback gain optimization and equivalent power reference limitation method are further given to increase the robustness against large impedance measurement error. Based on equal area criterion, it is demonstrated that with the proposed hybrid power synchronization method, the transient stability of GFM voltage source converter always can be guaranteed once the SEP exists. The impact of line-to-ground fault on transient stability is analyzed and the robust enhanced method is also given. Finally, the effectiveness of the proposed method is verified on a 5 kW experimental platform.

IEEE Transactions on Power ElectronicsVol. 40(2)
Wuhan University (CN), China Electric Equipment Group (China) (CN), China Electric Power Research Institute
Affordable and clean energy
Openalex Percentile: Top 11%
Power Systems and Renewable Energy
2.54
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.