A novel fault ride through strategy for grid-connected virtual synchronous Generators: Power angle stability enhancement and current limiting

• Aiming at the problem that the VSG desynchronization during the fault, an AFDC strategy is designed to eliminate the power angle instability, and it is also beneficial to current limiting. • To protect VSG from being damaged by fault inrush current, a fault inrush current suppression method combining VI and reference voltage adjustment is proposed. As more and more renewable energy generations (REGs) are connected to the power grid through grid-following converters, the lack of inertia has become a challenge to grid-frequency stability. Virtual Synchronous Generator (VSG) is a prospected solution for this issue. However, VSGs still have several unresolved issues in practical application. Especially, in a three-phase symmetrical fault scenario, the inrush current may damage the converter and the VSG would lose synchronization with the grid. To address these issues, this paper presents a novel fault ride through (FRT) strategy. First, the transient behaviours of VSGs, including transient current characteristics and power angle characteristics are analysed, which reveals that the increase of the power angle would aggravate the inrush current. Thus, an angular frequency dynamic compensation (AFDC) strategy is proposed to eliminate the instability of power angle. Then, this paper presents a current-limiting strategy combining virtual impedance (VI) and reference voltage adjustment to limit the fault current to a safe level. Finally, the time-domain simulations and experimental tests are performed to verify the effectiveness of the proposed FRT strategy.

Authors

Institutions

Publication Details

Journal
International Journal of Electrical Power & Energy Systems
Published
2024-10-14
DOI
https://doi.org/10.1016/j.ijepes.2024.110293
Citations
5
Primary Topic
Microgrid Control and Optimization
Type
article
Field-Weighted Citation Impact
1.64
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

A novel fault ride through strategy for grid-connected virtual synchronous Generators: Power angle stability enhancement and current limiting

Siqi Liu, Wenbin Lin, Yanxue Yu, Pengfei Hu et al.
5 citations
International Journal of Electrical Power & Energy Systems
Microgrid Control and Optimization
1.64
article

A novel fault ride through strategy for grid-connected virtual synchronous Generators: Power angle stability enhancement and current limiting

Siqi Liu, Wenbin Lin, Yanxue Yu, Pengfei Hu, Zheng Chen, Daozhuo Jiang
article en
5 citations

Abstract

• Aiming at the problem that the VSG desynchronization during the fault, an AFDC strategy is designed to eliminate the power angle instability, and it is also beneficial to current limiting. • To protect VSG from being damaged by fault inrush current, a fault inrush current suppression method combining VI and reference voltage adjustment is proposed. As more and more renewable energy generations (REGs) are connected to the power grid through grid-following converters, the lack of inertia has become a challenge to grid-frequency stability. Virtual Synchronous Generator (VSG) is a prospected solution for this issue. However, VSGs still have several unresolved issues in practical application. Especially, in a three-phase symmetrical fault scenario, the inrush current may damage the converter and the VSG would lose synchronization with the grid. To address these issues, this paper presents a novel fault ride through (FRT) strategy. First, the transient behaviours of VSGs, including transient current characteristics and power angle characteristics are analysed, which reveals that the increase of the power angle would aggravate the inrush current. Thus, an angular frequency dynamic compensation (AFDC) strategy is proposed to eliminate the instability of power angle. Then, this paper presents a current-limiting strategy combining virtual impedance (VI) and reference voltage adjustment to limit the fault current to a safe level. Finally, the time-domain simulations and experimental tests are performed to verify the effectiveness of the proposed FRT strategy.

International Journal of Electrical Power & Energy SystemsVol. 162
Fujian Electric Power Survey & Design Institute (CN), Zhejiang University (CN)
Affordable and clean energy
Openalex Percentile: Top 16%
Microgrid Control and Optimization
1.64
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.