STUDY ON THE TESTING OF POWER BREAKERS (PMT) IN THE 150 KV TRANSFORMER BAY AT THE PANAKKUKANG SUBSTATION

The Circuit Breaker (PMT) plays a very important role in the substation system because the PMT is the equipment responsible for disconnecting the load current during a disturbance. This study aims to determine the results of insulation resistance testing, contact resistance testing, and simultaneity of the Circuit Breaker (PMT), evaluate the quality of the PMT, and determine the results of the NGR (Neutral Grounding Resistor) testing at the Panakkukang Substation. This research employs a quantitative method using an ex post facto research design. The research was conducted at PT. PLN (Persero) Panakkukang Substation, with the object being the 150 kV transformer bay Circuit Breaker (PMT). The results obtained from this study show that the insulation materials and contact components of the Circuit Breaker installed in transformer bay 2 are still in good and safe condition. The Circuit Breaker can trip according to normal simultaneity performance. The quality of the PMT is still in safe and operational condition, and the NGR (Neutral Ground Resistor) test results for transformer bay 2 indicate that it is still in good and safe condition.

Authors

Institutions

Publication Details

Journal
Journal of Electrical Engineering and Informatics
Published
2024-10-11
DOI
https://doi.org/10.59562/jeeni.v2i1.4552
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

STUDY ON THE TESTING OF POWER BREAKERS (PMT) IN THE 150 KV TRANSFORMER BAY AT THE PANAKKUKANG SUBSTATION

Fathahillah Fathahillah, Zulhajji Zulhajji, Fardian Salam
Journal of Electrical Engineering and Informatics
Power Transformer Diagnostics and Insulation
article

STUDY ON THE TESTING OF POWER BREAKERS (PMT) IN THE 150 KV TRANSFORMER BAY AT THE PANAKKUKANG SUBSTATION

Fathahillah Fathahillah, Zulhajji Zulhajji, Fardian Salam
article en

Abstract

The Circuit Breaker (PMT) plays a very important role in the substation system because the PMT is the equipment responsible for disconnecting the load current during a disturbance. This study aims to determine the results of insulation resistance testing, contact resistance testing, and simultaneity of the Circuit Breaker (PMT), evaluate the quality of the PMT, and determine the results of the NGR (Neutral Grounding Resistor) testing at the Panakkukang Substation. This research employs a quantitative method using an ex post facto research design. The research was conducted at PT. PLN (Persero) Panakkukang Substation, with the object being the 150 kV transformer bay Circuit Breaker (PMT). The results obtained from this study show that the insulation materials and contact components of the Circuit Breaker installed in transformer bay 2 are still in good and safe condition. The Circuit Breaker can trip according to normal simultaneity performance. The quality of the PMT is still in safe and operational condition, and the NGR (Neutral Ground Resistor) test results for transformer bay 2 indicate that it is still in good and safe condition.

Journal of Electrical Engineering and InformaticsVol. 2(1)
State University of Makassar (ID)
Openalex Percentile: Top 85%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.