Cost-effective reliability level in 100% renewables-based standalone microgrids considering investment and expected energy not served costs

Loss of load probability (LOLP) and expected energy not served (EENS) are commonly used in electrical power systems to evaluate reliability. LOLP defined as the probability that available generation capacity will be inadequate to supply customer demand. EENS defined as the expected amount of energy not being served to consumers by the system during the period considered due to system capacity shortages or unexpected power outages. Loss of Load Frequency (LOLF) is referred to a number of loss of load (LOL) event happened in the operation life span of the SMG. Loss of Load Reduction (LOLR) is defined as the required reduction in LOLF to obtain a specific reliability level. While power systems are designed to minimize LOLP and EENS, this is constrained by the total cost: investment cost, operation and maintenance cost, and cost of customer interruption (CCI). This research considers Standalone Microgrid (SMG), also known as Autonomous Microgrid which only operates in off-grid mode and cannot be connected to wider electrical power system. When designing a 100% renewable energy integrated SMGs, it is crucial to determine the cost-effective reliability level (CERL). The CERL occurs when the total cost is minimum. This research proposes an approach to calculate the CERL for a fully renewable SMG. An analytical formulation is proposed to represent the LOLR needed to obtain a specific reliability level as a function of the required size of reliability improvement alternatives. The CCI is evaluated using LOLF and EENS indices. Finally, the total cost of the SMG system is evaluated for each reliability level. Consequently, the total cost of the SMG system is expressed as a function of reliability levels, and the minimum value of total cost and the corresponding reliability level are evaluated. In this research, a Monte Carlo Simulation (MCS) approach is used to find hourly LOLF, considering 25 years (219,000 hours) of SMG lifespan, regression analysis is used for an analytical formulation, and mixed integer linear programming (MILP) is used for the investment decision making based on a cost minimization approach. The result demonstrates that the CERL of the SMG system evaluated in the case study is 98.71%. • Monte Carlo simulation is used for loss of load frequency over 25 years. • Cost-effective reliability level of SMG is evaluated using total cost curve. • The failure analysis is performed in a hybrid renewable energy SMG system. • Curve fitting technique is used to determine various equations. • To minimize total cost, SMG should be operated at 98.25% reliability.

Authors

Institutions

Publication Details

Journal
Energy
Published
2024-10-12
DOI
https://doi.org/10.1016/j.energy.2024.133426
Citations
10
Primary Topic
Hybrid Renewable Energy Systems
Type
article
Field-Weighted Citation Impact
1.70
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Cost-effective reliability level in 100% renewables-based standalone microgrids considering investment and expected energy not served costs

S. M. Muyeen, Ali Arefi, C.P. Lund, Sakthivelnathan Nallainathan et al.
10 citations
Energy
Hybrid Renewable Energy Systems
1.70
article

Cost-effective reliability level in 100% renewables-based standalone microgrids considering investment and expected energy not served costs

S. M. Muyeen, Ali Arefi, C.P. Lund, Sakthivelnathan Nallainathan, Ali Mehrizi‐Sani
article en
10 citations

Abstract

Loss of load probability (LOLP) and expected energy not served (EENS) are commonly used in electrical power systems to evaluate reliability. LOLP defined as the probability that available generation capacity will be inadequate to supply customer demand. EENS defined as the expected amount of energy not being served to consumers by the system during the period considered due to system capacity shortages or unexpected power outages. Loss of Load Frequency (LOLF) is referred to a number of loss of load (LOL) event happened in the operation life span of the SMG. Loss of Load Reduction (LOLR) is defined as the required reduction in LOLF to obtain a specific reliability level. While power systems are designed to minimize LOLP and EENS, this is constrained by the total cost: investment cost, operation and maintenance cost, and cost of customer interruption (CCI). This research considers Standalone Microgrid (SMG), also known as Autonomous Microgrid which only operates in off-grid mode and cannot be connected to wider electrical power system. When designing a 100% renewable energy integrated SMGs, it is crucial to determine the cost-effective reliability level (CERL). The CERL occurs when the total cost is minimum. This research proposes an approach to calculate the CERL for a fully renewable SMG. An analytical formulation is proposed to represent the LOLR needed to obtain a specific reliability level as a function of the required size of reliability improvement alternatives. The CCI is evaluated using LOLF and EENS indices. Finally, the total cost of the SMG system is evaluated for each reliability level. Consequently, the total cost of the SMG system is expressed as a function of reliability levels, and the minimum value of total cost and the corresponding reliability level are evaluated. In this research, a Monte Carlo Simulation (MCS) approach is used to find hourly LOLF, considering 25 years (219,000 hours) of SMG lifespan, regression analysis is used for an analytical formulation, and mixed integer linear programming (MILP) is used for the investment decision making based on a cost minimization approach. The result demonstrates that the CERL of the SMG system evaluated in the case study is 98.71%. • Monte Carlo simulation is used for loss of load frequency over 25 years. • Cost-effective reliability level of SMG is evaluated using total cost curve. • The failure analysis is performed in a hybrid renewable energy SMG system. • Curve fitting technique is used to determine various equations. • To minimize total cost, SMG should be operated at 98.25% reliability.

EnergyVol. 311
Murdoch University (AU), Bradley University (US), Qatar University (QA), Virginia Tech (US)
Affordable and clean energy
Openalex Percentile: Top 16%
Hybrid Renewable Energy Systems
1.70
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.