Experimental Analysis of Aging of a Dry Transformer: Comparison of Two Methods for PD Measurements

Dry-type transformers require little maintenance and are more environmentally friendly with respect to traditional oil-and-paper design. However, partial discharges (PDs) and thermal stress may lead to aging and—eventually—failure of the insulation. Diagnostics of their conditions—often performed by means of PD measurement—can be tricky, as PD activity depends on many parameters. In this work, a cast-resin power transformer is aged by means of 28 heating/cooling thermal cycles, to reproduce the thermal–electrical stress it may experience in operation. PD activity is monitored during the cooling branch of each cycle using a high-frequency current transformer (HFCT) to measure the current bled to the ground by the transformer shield, whose results are compared to the apparent charge measured by an IEC 60270-compliant commercial system installed on the medium-voltage (MV) winding. The effect of temperature and aging (number of cycles) is then investigated. The results show good agreement between the two measuring systems, in terms of both the phase-resolved partial discharge (PRPD) patterns and the average intensity trend over time. According to the intensity dependence on temperature, two PD series were identified: one series shows a loose dependence on temperature, and the other one a strong dependence. It was speculated that two types of defects may exist, whose geometry (and hence PD activity) may be affected by temperature to different extents (e.g., due to their position). Finally, a decrease in PD rate in time was observed, without a significant reduction of the average discharge intensity, which is supposedly due to different aging rates of different defects.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Dielectrics and Electrical Insulation
Published
2024-10-11
DOI
https://doi.org/10.1109/tdei.2024.3479131
Citations
1
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.21
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental Analysis of Aging of a Dry Transformer: Comparison of Two Methods for PD Measurements

Daniele Palladini, Luca Barbieri, Andrea Villa, M. Sozzi et al.
1 citations
IEEE Transactions on Dielectrics and Electrical Insulation
Power Transformer Diagnostics and Insulation
0.21
article

Experimental Analysis of Aging of a Dry Transformer: Comparison of Two Methods for PD Measurements

Daniele Palladini, Luca Barbieri, Andrea Villa, M. Sozzi, Giovanni D’Avanzo, Giacomo Buccella, Damiano Fasani, Simone Venturini
article en
1 citations

Abstract

Dry-type transformers require little maintenance and are more environmentally friendly with respect to traditional oil-and-paper design. However, partial discharges (PDs) and thermal stress may lead to aging and—eventually—failure of the insulation. Diagnostics of their conditions—often performed by means of PD measurement—can be tricky, as PD activity depends on many parameters. In this work, a cast-resin power transformer is aged by means of 28 heating/cooling thermal cycles, to reproduce the thermal–electrical stress it may experience in operation. PD activity is monitored during the cooling branch of each cycle using a high-frequency current transformer (HFCT) to measure the current bled to the ground by the transformer shield, whose results are compared to the apparent charge measured by an IEC 60270-compliant commercial system installed on the medium-voltage (MV) winding. The effect of temperature and aging (number of cycles) is then investigated. The results show good agreement between the two measuring systems, in terms of both the phase-resolved partial discharge (PRPD) patterns and the average intensity trend over time. According to the intensity dependence on temperature, two PD series were identified: one series shows a loose dependence on temperature, and the other one a strong dependence. It was speculated that two types of defects may exist, whose geometry (and hence PD activity) may be affected by temperature to different extents (e.g., due to their position). Finally, a decrease in PD rate in time was observed, without a significant reduction of the average discharge intensity, which is supposedly due to different aging rates of different defects.

IEEE Transactions on Dielectrics and Electrical InsulationVol. 32(3)
Ricerca sul Sistema Energetico (Italy) (IT)
Openalex Percentile: Top 47%
Power Transformer Diagnostics and Insulation
0.21
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.