An Exergetic Performance Improvement Potential of a Modified Ejector-Enhanced Auto-Cascade Refrigeration Cycle
This study examines both conventional and advanced exergy analyses of a modified ejector-enhanced auto-cascade refrigeration (MEACR) cycle. Conventional exergy analysis shows that the proposed model significantly improves exergy efficiency compared to similar ejector-enhanced auto-cascade refrigeration cycles in the literature. Advanced exergy analysis reveals that 63.47% of the total exergy destruction is avoidable. When the components of the MEACR cycle are investigated, 56.31% of the exergy destruction is attributed to the endogenous part. The low-temperature cycle (LTC) compressor has the highest avoidable endogenous exergy destruction rate of 12.64 kW with 38.5%.
Authors
- Arif Hepbaşlı
- Ibrahim Karacayli (ORCID: https://orcid.org/0000-0002-4459-1450)
- Lütfiye Altay (ORCID: https://orcid.org/0000-0003-4946-3615)
Institutions
- Ege University (TR)
- Yaşar University (TR)
Publication Details
- Journal
- International Journal of Exergy
- Published
- 2024-10-11
- DOI
- https://doi.org/10.1504/ijex.2025.10067148
- Primary Topic
- Refrigeration and Air Conditioning Technologies
- Type
- article
- Field-Weighted Citation Impact
- 0.00