Numerical Analysis of Partial Discharge Ignition in H₂ Bubbles Floating in Dielectric Oils, for High-Voltage Solid State Transformer Applications

We report on a self-consistent numerical analysis campaign of partial discharge (PD) ignition in H2 bubbles floating in biobased dielectric oils. We investigate various configurations (bubble sizes, bubble position, and existence of protrusion) on a cylinder-to-cylinder setup that emulates a specific SST module (from SSTAR Horizon Europe project) under transient overvoltage as well as in its design operational conditions (<inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">${V} _{\text {RMS}} =66$ </tex-math></inline-formula> kV, ac excitation of 50 Hz). Our results on electrical characteristics and plasma dynamics leading to the PD ignition, indicate that under transient overvoltage and for mm size bubbles (diameter 1–4.5 mm), the smaller the bubble, the less the inception voltage, while the peak inception voltage is higher than 70 kV. The existence of metallic protrusion can affect the inception voltage of a remote floating bubble only slightly and when this is close to the sharp tip. The extreme scenario of a protrusion in contact (inside) a gas bubble severely affects the insulation properties and drops the PD inception voltage remarkably. The larger the bubble and the sharper the tip of the protrusion, the lower the inception peak voltage, that can reach values well below 40 kV. On the contrary and under design operation, larger bubbles increase the severity and probability of PD events, leading to lower instantaneous inception voltages. Current pulses produced in bubbles can quickly transit to intense streamer discharges (which can also transit to catastrophic arcing) if the operational frequency is reduced and/or under transient, high-frequency (HF) overvoltage.

Authors

Institutions

Publication Details

Journal
IEEE Transactions on Dielectrics and Electrical Insulation
Published
2024-10-10
DOI
https://doi.org/10.1109/tdei.2024.3478130
Primary Topic
Power Transformer Diagnostics and Insulation
Type
article
Field-Weighted Citation Impact
0.00

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Numerical Analysis of Partial Discharge Ignition in H₂ Bubbles Floating in Dielectric Oils, for High-Voltage Solid State Transformer Applications

Panagiotis Dimitrakellis, Dimitrios Rakopoulos, Konstantinos Kourtzanidis
IEEE Transactions on Dielectrics and Electrical Insulation
Power Transformer Diagnostics and Insulation
article

Numerical Analysis of Partial Discharge Ignition in H₂ Bubbles Floating in Dielectric Oils, for High-Voltage Solid State Transformer Applications

Panagiotis Dimitrakellis, Dimitrios Rakopoulos, Konstantinos Kourtzanidis
article en

Abstract

We report on a self-consistent numerical analysis campaign of partial discharge (PD) ignition in H2 bubbles floating in biobased dielectric oils. We investigate various configurations (bubble sizes, bubble position, and existence of protrusion) on a cylinder-to-cylinder setup that emulates a specific SST module (from SSTAR Horizon Europe project) under transient overvoltage as well as in its design operational conditions (<inline-formula xmlns:mml="http://www.w3.org/1998/Math/MathML" xmlns:xlink="http://www.w3.org/1999/xlink"> <tex-math notation="LaTeX">${V} _{\text {RMS}} =66$ </tex-math></inline-formula> kV, ac excitation of 50 Hz). Our results on electrical characteristics and plasma dynamics leading to the PD ignition, indicate that under transient overvoltage and for mm size bubbles (diameter 1–4.5 mm), the smaller the bubble, the less the inception voltage, while the peak inception voltage is higher than 70 kV. The existence of metallic protrusion can affect the inception voltage of a remote floating bubble only slightly and when this is close to the sharp tip. The extreme scenario of a protrusion in contact (inside) a gas bubble severely affects the insulation properties and drops the PD inception voltage remarkably. The larger the bubble and the sharper the tip of the protrusion, the lower the inception peak voltage, that can reach values well below 40 kV. On the contrary and under design operation, larger bubbles increase the severity and probability of PD events, leading to lower instantaneous inception voltages. Current pulses produced in bubbles can quickly transit to intense streamer discharges (which can also transit to catastrophic arcing) if the operational frequency is reduced and/or under transient, high-frequency (HF) overvoltage.

IEEE Transactions on Dielectrics and Electrical InsulationVol. 32(3)
Centre for Research and Technology Hellas (GR)
HORIZON EUROPE Framework Programme
Affordable and clean energy
Openalex Percentile: Top 85%
Power Transformer Diagnostics and Insulation
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.