Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency

This study presents a comprehensive numerical analysis of thermal performance and energy efficiency, IT operating environment, and thermal performance of the RDHx system, a rack-based cooling solution for high-density IT power using air-cooled equipment. A 150 kW IT module and RDHx cooling system were designed and evaluated, and CFD numerical analysis confirmed that RDHx maintains a stable IT environment within ASHRAE standards at a supply air temperature of 24°C. Additionally, the chilled water supply temperature for the secondary CDU can be increased to 14°C, and for the primary chiller to 12°C. A central chilled water system for a 30 MW reference data center was designed and analyzed, showing increased efficiency with a 12°C supply temperature and varying condenser water return temperatures in winter, resulting in an annual PUE cooling range of 1.25 to 1.33, with an average of 1.27. The annual energy consumption distribution for rack-based cooling is approximately 46% from chillers, 21% from fans, and 33% from pumps. These results provide crucial insights into data center cooling and support the application of the RDHx system in high-density data centers, with future validation involving a field mock-up test of a 150 kW IT module.

Authors

Institutions

Publication Details

Journal
Case Studies in Thermal Engineering
Published
2024-10-05
DOI
https://doi.org/10.1016/j.csite.2024.105247
Citations
10
Primary Topic
Heat Transfer and Optimization
Type
article
Field-Weighted Citation Impact
2.13

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency

Jinkyun Cho
10 citations
Case Studies in Thermal Engineering
Heat Transfer and Optimization
2.13
article

Numerical analysis of rack-based data center cooling with rear door heat exchanger (RDHx): Interrelationship between thermal performance and energy efficiency

Jinkyun Cho
article en
10 citations

Abstract

This study presents a comprehensive numerical analysis of thermal performance and energy efficiency, IT operating environment, and thermal performance of the RDHx system, a rack-based cooling solution for high-density IT power using air-cooled equipment. A 150 kW IT module and RDHx cooling system were designed and evaluated, and CFD numerical analysis confirmed that RDHx maintains a stable IT environment within ASHRAE standards at a supply air temperature of 24°C. Additionally, the chilled water supply temperature for the secondary CDU can be increased to 14°C, and for the primary chiller to 12°C. A central chilled water system for a 30 MW reference data center was designed and analyzed, showing increased efficiency with a 12°C supply temperature and varying condenser water return temperatures in winter, resulting in an annual PUE cooling range of 1.25 to 1.33, with an average of 1.27. The annual energy consumption distribution for rack-based cooling is approximately 46% from chillers, 21% from fans, and 33% from pumps. These results provide crucial insights into data center cooling and support the application of the RDHx system in high-density data centers, with future validation involving a field mock-up test of a 150 kW IT module.

Case Studies in Thermal EngineeringVol. 63
Hanbat National University (KR)
Ministry of Science and ICT, South Korea
Affordable and clean energy
Openalex Percentile: Top 13%
Heat Transfer and Optimization
2.13
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.