Assessment of Quasi-Stationary Power Quality Phenomena in DC Power Systems

• The paper focuses on the main quasi-stationary PQ (Power Quality) disturbances commonly encountered in dc power systems, i.e., dc magnitude deviation and ripple. • For the most common indices used for quantifying the intensity of these phenomena (average and rms dc magnitude, rms and peak-to-peak value of ripple, spectral component amplitudes of ripple), measurement procedures, commonly adopted, are analyzed and discussed, through analytical modeling and experimental applications, considering important aspects that affect the accuracy and reliability of results in field measurements: reciprocal effects of the presence of PQ phenomena, desynchronization of the analyses, presence of noise, and quantization due to analog-to-digital conversion. • Then, advanced signal processing methods, suitable to be adopted in standards for dc PQ compatibility level surveys, are proposed to improve the accuracy and reliability of results. • For analysis in the time domain, the presented procedures are aimed at the mitigation of the effects of spikes, noise, and slow variations. • For analysis in the frequency domain, a practical method of grouping spectral components, similar to that adopted for harmonics in ac systems, is proposed to cope with spectral dispersion of ripple components. • The presented procedures are applied to a concrete measurement situation of a real LVDC (Low Voltage Direct Current) grid. The adoption of dc architectures for electricity distribution has been increasingly considered to reduce the number of energy conversions and to exploit their inherent ability to cope with peaks in energy supply and demand. Furthermore, dc systems have been commonly and widely adopted for high-voltage transmission systems and public transport for many years. Despite this, the Power Quality (PQ) assessment in dc power networks is still unstandardized. In the scientific literature, various indices have been proposed for the quantification of dc PQ. However, not all the aspects encountered in practical applications are adequately accounted for, and their effects regarding the impact on the measurement results are not fully analysed. This paper focuses on signal processing for the analysis of PQ of dc networks in stationary or quasi-stationary conditions aimed at compatibility level assessment. The influence quantities that affect the measurement results of the most commonly adopted procedures for determining the PQ index determination are identified and modelled, and their impact is analytically calculated. Advanced signal processing methods, suitable to be adopted in standards for dc PQ compatibility level surveys, are proposed to improve the accuracy and reliability of results. The rationality and effectiveness of the proposed procedures are shown with analytical calculations and in real measurement situations.

Authors

Institutions

Publication Details

Journal
Measurement
Published
2024-09-30
DOI
https://doi.org/10.1016/j.measurement.2024.115844
Citations
4
Primary Topic
HVDC Systems and Fault Protection
Type
article
Field-Weighted Citation Impact
0.83

Funders

Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Assessment of Quasi-Stationary Power Quality Phenomena in DC Power Systems

Mario Luiso, Helko E. van den Brom, Antonio Delle Femine, Ronald van Leeuwen et al.
4 citations
Measurement
HVDC Systems and Fault Protection
0.83
article

Assessment of Quasi-Stationary Power Quality Phenomena in DC Power Systems

Mario Luiso, Helko E. van den Brom, Antonio Delle Femine, Ronald van Leeuwen, Carmine Landi, Daniele Gallo
article en
4 citations

Abstract

• The paper focuses on the main quasi-stationary PQ (Power Quality) disturbances commonly encountered in dc power systems, i.e., dc magnitude deviation and ripple. • For the most common indices used for quantifying the intensity of these phenomena (average and rms dc magnitude, rms and peak-to-peak value of ripple, spectral component amplitudes of ripple), measurement procedures, commonly adopted, are analyzed and discussed, through analytical modeling and experimental applications, considering important aspects that affect the accuracy and reliability of results in field measurements: reciprocal effects of the presence of PQ phenomena, desynchronization of the analyses, presence of noise, and quantization due to analog-to-digital conversion. • Then, advanced signal processing methods, suitable to be adopted in standards for dc PQ compatibility level surveys, are proposed to improve the accuracy and reliability of results. • For analysis in the time domain, the presented procedures are aimed at the mitigation of the effects of spikes, noise, and slow variations. • For analysis in the frequency domain, a practical method of grouping spectral components, similar to that adopted for harmonics in ac systems, is proposed to cope with spectral dispersion of ripple components. • The presented procedures are applied to a concrete measurement situation of a real LVDC (Low Voltage Direct Current) grid. The adoption of dc architectures for electricity distribution has been increasingly considered to reduce the number of energy conversions and to exploit their inherent ability to cope with peaks in energy supply and demand. Furthermore, dc systems have been commonly and widely adopted for high-voltage transmission systems and public transport for many years. Despite this, the Power Quality (PQ) assessment in dc power networks is still unstandardized. In the scientific literature, various indices have been proposed for the quantification of dc PQ. However, not all the aspects encountered in practical applications are adequately accounted for, and their effects regarding the impact on the measurement results are not fully analysed. This paper focuses on signal processing for the analysis of PQ of dc networks in stationary or quasi-stationary conditions aimed at compatibility level assessment. The influence quantities that affect the measurement results of the most commonly adopted procedures for determining the PQ index determination are identified and modelled, and their impact is analytically calculated. Advanced signal processing methods, suitable to be adopted in standards for dc PQ compatibility level surveys, are proposed to improve the accuracy and reliability of results. The rationality and effectiveness of the proposed procedures are shown with analytical calculations and in real measurement situations.

MeasurementVol. 242
University of Campania "Luigi Vanvitelli" (IT), VSL National Metrology Institute (NL)
European Metrology Programme for Innovation and Research
Affordable and clean energy
Openalex Percentile: Top 27%
HVDC Systems and Fault Protection
0.83
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.