Evaluating common supply air temperature setpoint reset strategies with varying occupancy patterns and behaviours

The supply air temperature (SAT) setpoint of a multi-zone variable air volume (VAV) air handling unit (AHU) systems significantly affects the system’s performance. ASHRAE Guideline 36 introduces a so-called trim and respond logic defining the SAT reset behaviour of these systems. The trim and respond logic for SAT reset relies on demand-based feedback. Many studies have assessed ASHRAE Guideline 36, however there is a literature gap in addressing the performance of the trim and respond SAT reset with varying occupancy patterns and behaviours. This paper studies four SAT reset strategies under different thermal preferences and irregular occupancy patterns: (1) constant 13°C SAT, (2) SAT reset based on outdoor air temperature (OAT), (3) trim and respond, and (4) trim and respond combined with OAT reset. Different cases of zone-level setpoints and irregular occupancy schedules have been simulated in EnergyPlus with the studied SAT setpoint reset methods. The results show that varying setpoints across different zones lead to higher energy use with all studied SAT reset strategies. The highest variation in energy use was accompanied with constant SAT, with a standard deviation of 16 kWh/m 2 , and the highest variation in averaged discomfort fraction was accompanied with OAT reset, with a standard deviation of 5.3%. Both trim and respond methods achieved better comfort results with varying setpoints. These findings establish a basis for future work on developing a SAT reset strategy that utilizes occupant-centric control (OCC) that optimally balances thermal comfort and energy use. • Studying supply air temperature reset strategies with varying occupancy behaviour. • Pure trim and respond consumed least energy with varying zone setpoints. • Varying zone setpoints did not affect comfort with trim and respond SAT reset. • Simultaneous cooling and heating occurred due to conflicting zone demands.

Authors

Institutions

Publication Details

Journal
Building and Environment
Published
2024-09-28
DOI
https://doi.org/10.1016/j.buildenv.2024.112129
Citations
7
Primary Topic
Building Energy and Comfort Optimization
Type
article
Field-Weighted Citation Impact
1.86
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Evaluating common supply air temperature setpoint reset strategies with varying occupancy patterns and behaviours

Mohamed M. Ouf, Nunzio Cotrufo, Jean-Simon Venne, Hussein Elehwany et al.
7 citations
Building and Environment
Building Energy and Comfort Optimization
1.86
article

Evaluating common supply air temperature setpoint reset strategies with varying occupancy patterns and behaviours

Mohamed M. Ouf, Nunzio Cotrufo, Jean-Simon Venne, Hussein Elehwany, Burak Gunay
article en
7 citations

Abstract

The supply air temperature (SAT) setpoint of a multi-zone variable air volume (VAV) air handling unit (AHU) systems significantly affects the system’s performance. ASHRAE Guideline 36 introduces a so-called trim and respond logic defining the SAT reset behaviour of these systems. The trim and respond logic for SAT reset relies on demand-based feedback. Many studies have assessed ASHRAE Guideline 36, however there is a literature gap in addressing the performance of the trim and respond SAT reset with varying occupancy patterns and behaviours. This paper studies four SAT reset strategies under different thermal preferences and irregular occupancy patterns: (1) constant 13°C SAT, (2) SAT reset based on outdoor air temperature (OAT), (3) trim and respond, and (4) trim and respond combined with OAT reset. Different cases of zone-level setpoints and irregular occupancy schedules have been simulated in EnergyPlus with the studied SAT setpoint reset methods. The results show that varying setpoints across different zones lead to higher energy use with all studied SAT reset strategies. The highest variation in energy use was accompanied with constant SAT, with a standard deviation of 16 kWh/m 2 , and the highest variation in averaged discomfort fraction was accompanied with OAT reset, with a standard deviation of 5.3%. Both trim and respond methods achieved better comfort results with varying setpoints. These findings establish a basis for future work on developing a SAT reset strategy that utilizes occupant-centric control (OCC) that optimally balances thermal comfort and energy use. • Studying supply air temperature reset strategies with varying occupancy behaviour. • Pure trim and respond consumed least energy with varying zone setpoints. • Varying zone setpoints did not affect comfort with trim and respond SAT reset. • Simultaneous cooling and heating occurred due to conflicting zone demands.

Building and EnvironmentVol. 266
Brain Canada Foundation (CA), Concordia University (CA), Carleton University (CA)
Affordable and clean energy
Openalex Percentile: Top 16%
Building Energy and Comfort Optimization
1.86
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.