Fault-Tolerant Control for One-Phase Current Sensor Fault in Open-End Winding PMSM fed by Dual Inverter With a Common DC Bus
This letter presents a fault-tolerant control (FTC) for a one-phase current sensor failure in the open-ended winding permanent magnet synchronous motor (PMSM) fed by the dual inverter with a common dc bus. While many FTC strategies for stator winding and inverter leg faults have been researched, an FTC for one-phase current sensor fault has not yet been proposed. Unlike a single inverter, the dual inverter with a common dc bus needs three-phase current measurement due to the flow of zero-sequence current (ZSC). A one-phase current sensor fault can result in immediate system shutdown or severe degradation in control performance. This study proposes a method for estimating the one-phase current using the currents from the other two phases. Both the FTC and the ZSC control can be implemented in the presence of a one-phase current sensor fault. Experimental results are provided to validate the proposed method.