Performance analysis of a solar-assisted ground source heat pump with a single vertical U-tube ground heat exchanger

• SAGSHP operations for optimal cold climate performance are presented. • Realistic building energy and solar loads are coupled with a single U-tube SAGSHP. • Influence of solar collector tilt angle and GHE configurations are investigated. • The highest annual heating COP and energy savings are achieved with 45° tilt angle. • Single U-tube SAGSHP performs better for heating operations but not for cooling. Owing to higher heat loads than cooling loads in cold climates, the performance of ground source heat pumps (GSHPs) can significantly degrade over time, leading to eventual system failure for systems not properly sized or when there is insufficient regeneration. Solar-assisted ground source heat pump (SAGSHP) systems are receiving increasing interest as a means of enhancing heating performance and maintaining ground thermal balance in cold regions. However, a critical gap remains in the literature: no study has comprehensively analyzed configurations of SAGSHP systems to enhance their overall performance considering long-term performance and realistic operating conditions. For this purpose, a comprehensive investigation of the long-term performance of single U-tube and double U-tube ground heat exchangers (GHEs) for solar-assisted ground source heat pump systems (SAGSHPs) was carried out and compared with the conventional GSHP. The effect of collector tilt angles (0–90°) on the performance of the single U-tube SAGSHP was also examined. A finite volume computational fluid dynamic model was developed and coupled with an actual building energy load profile and a solar irradiation profile based on Calgary’s weather conditions using a novel custom-coded thermodynamic model. Results show that the yearly average heating coefficient of performance (COP) increases by a factor of 1.21 and 1.18 for the single U-tube SAGSHP and double U-tube SAGSHP, respectively, when compared with the conventional GSHP. However, the average annual cooling COP reduces by 0.65 for the single U-tube and 0.72 for the double U-tube SAGSHPs. Moreover, considering the effect of tilt angle on the single U-tube SAGSHP, it is possible to improve the cooling COP when the collector tilt angle is 90°, at the expense of lower heating COP. However, the highest heating COP and annual energy savings are achieved with a tilt angle of 45°. This study provides practical insight into SAGSHP performance enhancements in cold climates.

Authors

Institutions

Publication Details

Journal
Applied Thermal Engineering
Published
2024-09-23
DOI
https://doi.org/10.1016/j.applthermaleng.2024.124452
Citations
19
Primary Topic
Geothermal Energy Systems and Applications
Type
article
Field-Weighted Citation Impact
1.95
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Performance analysis of a solar-assisted ground source heat pump with a single vertical U-tube ground heat exchanger

A. A. Mohamad, Roman Shor, Carsten Wemhöner, Aggrey Mwesigye et al.
19 citations
Applied Thermal Engineering
Geothermal Energy Systems and Applications
1.95
article

Performance analysis of a solar-assisted ground source heat pump with a single vertical U-tube ground heat exchanger

A. A. Mohamad, Roman Shor, Carsten Wemhöner, Aggrey Mwesigye, Philip Adebayo
article en
19 citations

Abstract

• SAGSHP operations for optimal cold climate performance are presented. • Realistic building energy and solar loads are coupled with a single U-tube SAGSHP. • Influence of solar collector tilt angle and GHE configurations are investigated. • The highest annual heating COP and energy savings are achieved with 45° tilt angle. • Single U-tube SAGSHP performs better for heating operations but not for cooling. Owing to higher heat loads than cooling loads in cold climates, the performance of ground source heat pumps (GSHPs) can significantly degrade over time, leading to eventual system failure for systems not properly sized or when there is insufficient regeneration. Solar-assisted ground source heat pump (SAGSHP) systems are receiving increasing interest as a means of enhancing heating performance and maintaining ground thermal balance in cold regions. However, a critical gap remains in the literature: no study has comprehensively analyzed configurations of SAGSHP systems to enhance their overall performance considering long-term performance and realistic operating conditions. For this purpose, a comprehensive investigation of the long-term performance of single U-tube and double U-tube ground heat exchangers (GHEs) for solar-assisted ground source heat pump systems (SAGSHPs) was carried out and compared with the conventional GSHP. The effect of collector tilt angles (0–90°) on the performance of the single U-tube SAGSHP was also examined. A finite volume computational fluid dynamic model was developed and coupled with an actual building energy load profile and a solar irradiation profile based on Calgary’s weather conditions using a novel custom-coded thermodynamic model. Results show that the yearly average heating coefficient of performance (COP) increases by a factor of 1.21 and 1.18 for the single U-tube SAGSHP and double U-tube SAGSHP, respectively, when compared with the conventional GSHP. However, the average annual cooling COP reduces by 0.65 for the single U-tube and 0.72 for the double U-tube SAGSHPs. Moreover, considering the effect of tilt angle on the single U-tube SAGSHP, it is possible to improve the cooling COP when the collector tilt angle is 90°, at the expense of lower heating COP. However, the highest heating COP and annual energy savings are achieved with a tilt angle of 45°. This study provides practical insight into SAGSHP performance enhancements in cold climates.

Applied Thermal EngineeringVol. 257
University of Calgary (CA), OST - Ostschweizer Fachhochschule (CH), Texas A&M University (US)
Affordable and clean energy
Openalex Percentile: Top 14%
Geothermal Energy Systems and Applications
1.95
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.