Experimental study and statistical analysis of system performance parameters of a household freezer

• The cooling system parameters of a household freezer are evaluated under various input parameters covering door opening effects. • The output parameters related to cooling system performance are frost amount, recovery time and energy consumption. • The recovery time increases more than twice as the ambient temperature rises from 25 °C to 32 °C. • Energy consumption escalates about 5 % from half load to full load cabinet for 30 s door opening at 32 °C and 85 % relative humidity conditions. • There is a 66 % increase in frost amount for the increasing frequency from 20 to 30 s at 32 °C and 85 % relative humidity conditions. The present research comprehensively examines the influences of different input variables, such as cabinet load level, ambient temperature, relative humidity, door opening time and day, on the output parameters of frosting amount, recovery time, and total energy consumption of the upright domestic freezer following the door opening operation. Moreover, a holistic statistical methodology, which is known as the GLM-ANOVA, was implemented for determining the parametric experimental results. Meanwhile, the effects of binary interactions between the input factors on the output parameters were extensively evaluated using statistical methods. As a consequence, the amount of frost increases with an upward gradient as the load level within the cabinet escalates from 25 °C to 32 °C. Both the duration of door openings and the relative humidity level have a double impact on the frosting. Moreover, the duration required for the system to recover from half load to full load more than doubles with an increase in ambient temperature from 25 °C to 32 °C. On the other hand, at an outdoor temperature of 25 °C, the recovery time demonstrates a close to linear relationship with the load level of the cabinet. Furthermore, the duration of door openings and the load capacity within the cabinet are considered two important factors that simultaneously influence the daily energy consumption. The infiltration of ambient air into the freezer compartment and the presence of moisture in the air substantially increase the energy consumption, especially when the relative humidity fluctuates between 30 % and 65 % and the door opening duration stretches from 10 to 20 s, respectively.

Authors

Institutions

Publication Details

Journal
International Journal of Thermofluids
Published
2024-09-16
DOI
https://doi.org/10.1016/j.ijft.2024.100867
Citations
3
Primary Topic
Refrigeration and Air Conditioning Technologies
Type
article
Field-Weighted Citation Impact
0.64
Controls
|||
ALL TIME
JAN
FEB
MAR
APR
MAY
JUN
JUL
AUG
SEP
OCT
article

Experimental study and statistical analysis of system performance parameters of a household freezer

İbrahim Dinçer, Mutlu İpek
3 citations
International Journal of Thermofluids
Refrigeration and Air Conditioning Technologies
0.64
article

Experimental study and statistical analysis of system performance parameters of a household freezer

İbrahim Dinçer, Mutlu İpek
article en
3 citations

Abstract

• The cooling system parameters of a household freezer are evaluated under various input parameters covering door opening effects. • The output parameters related to cooling system performance are frost amount, recovery time and energy consumption. • The recovery time increases more than twice as the ambient temperature rises from 25 °C to 32 °C. • Energy consumption escalates about 5 % from half load to full load cabinet for 30 s door opening at 32 °C and 85 % relative humidity conditions. • There is a 66 % increase in frost amount for the increasing frequency from 20 to 30 s at 32 °C and 85 % relative humidity conditions. The present research comprehensively examines the influences of different input variables, such as cabinet load level, ambient temperature, relative humidity, door opening time and day, on the output parameters of frosting amount, recovery time, and total energy consumption of the upright domestic freezer following the door opening operation. Moreover, a holistic statistical methodology, which is known as the GLM-ANOVA, was implemented for determining the parametric experimental results. Meanwhile, the effects of binary interactions between the input factors on the output parameters were extensively evaluated using statistical methods. As a consequence, the amount of frost increases with an upward gradient as the load level within the cabinet escalates from 25 °C to 32 °C. Both the duration of door openings and the relative humidity level have a double impact on the frosting. Moreover, the duration required for the system to recover from half load to full load more than doubles with an increase in ambient temperature from 25 °C to 32 °C. On the other hand, at an outdoor temperature of 25 °C, the recovery time demonstrates a close to linear relationship with the load level of the cabinet. Furthermore, the duration of door openings and the load capacity within the cabinet are considered two important factors that simultaneously influence the daily energy consumption. The infiltration of ambient air into the freezer compartment and the presence of moisture in the air substantially increase the energy consumption, especially when the relative humidity fluctuates between 30 % and 65 % and the door opening duration stretches from 10 to 20 s, respectively.

International Journal of ThermofluidsVol. 24
Ontario Tech University (CA), Yıldız Technical University (TR), Arçelik (Turkey) (TR)
Zero hunger
Openalex Percentile: Top 36%
Refrigeration and Air Conditioning Technologies
0.64
AI Navigator

Ask Laika to Summarize, Analyze, and Connect papers live on the map.

Summarize Papers & Methodologies

Extract key findings, datasets, and comparative methods across publications.

Benchmark Rankings & Visual Analytics

Rank top research institutions, authors, funders, topics, and journals by Field-Weighted Citation Impact (FWCI) and paper volume with instant charts.

Connect Distant Disciplines

Bridge topological clusters on the map to find hidden collaborative intersections.